접지임피던스의 변동이 최소가 되는 동축형 탄소접지전극의 길이의 산정
暂无分享,去创建一个
For the surge currents like lightning or ground fault currents containing high frequency components which cause the electromagnetic interferences for the electronic devices and communication equipment, the grounding impedances give the significantly composite characteristics which are dependent on the frequency of surge currents. In this paper, the analytical model and method for determining the optimal length of the newly developed coaxial type carbon ground electrode which has a little fluctuation in grounding impedance with frequency. The length of minimizing the fluctuation of grounding impedance by changing frequency from 100[㎐] to 1[㎒] was determined, and the validity of this proposed method was confirmed by comparing with the simulated and measured data.