수직형 정수장 내 히트펌프 최적 설계

Raw-water source heat pump system in vertical water treatment facility was simulated by utilizing TRNSYS simulator and the building analysis program. When one unit of heat pump was applied to all air-conditioning zones the vertical water treatment facility average COP and electric power was found to be 4.1 and 6.7 kW, respectively. When two unit of heat pump was separately applied to each zone, average COP and electric power was found to be 3.9 and 7.54 kW, respectively.