Impact of Moving Objects onContaminant Concentration Distributions in an Inpatient Ward with Displacement Ventilation

Moving objects can disturb stratified flow and contaminant concentration gradient in an inpatient ward with displacement ventilation. This investigation uses computational fluid dynamics (CFD) to study the effect of objects moving, such as a visitor or caretaker walking, the changing of sheets on a patient's bed, and the swinging of an entrance door for up to four seconds, on the contaminant concentration distributions in a single inpatient ward. The CFD was validated by using the measured distributions of air velocity, air temperature, and contaminant concentration from the mockup of an inpatient ward. The contaminant was assumed to be breathed out by the patient lying on the bed. The results show that moving objects can cause a 10 to 90 second swing in the contaminant concentration distribution. The averaged concentration change in the breathing levels in the ward was generally less than 25%, so the risk level should remain the same. The closer the location of the moving object to the contaminant source, the larger was the change in the contaminant concentration. The displacement ventilation with 4 ach in an inpatient ward with a moving object can still produce the same air quality level as overhead mixing ventilation with 6 ach.

[1]  Chao-Hsin Lin,et al.  Flow dynamics and characterization of a cough. , 2009, Indoor air.

[2]  Magnus Mattsson,et al.  Displacement Ventilation: effects of movement and exhalation , 1997 .

[3]  Peter C Raynor,et al.  A performance assessment of airborne infection isolation rooms. , 2007, American journal of infection control.

[4]  Sagnik Mazumdar Transmission of airborne contaminants in airliner cabins , 2009 .

[5]  H Brohus,et al.  Influence of movements on contaminant transport in an operating room. , 2006, Indoor air.

[6]  Zhiqiang John Zhai,et al.  Evaluation of Various Turbulence Models in Predicting Airflow and Turbulence in Enclosed Environments by CFD: Part 2—Comparison with Experimental Data from Literature , 2007 .

[7]  A J Gadgil,et al.  Pollutant dispersion in a large indoor space. Part 2: Computational fluid dynamics predictions and comparison with a scale model experiment for isothermal flow. , 2004, Indoor air.

[8]  Zhiqiang Zhai,et al.  Design of a Ventilation System for an Indoor Auto Racing Complex , 2002 .

[9]  Zhao Zhang,et al.  Experimental and numerical investigation of airflow and contaminant transport in an airliner cabin mockup , 2009 .

[10]  P V Nielsen,et al.  Role of ventilation in airborne transmission of infectious agents in the built environment - a multidisciplinary systematic review. , 2007, Indoor air.

[11]  Chao-Hsin Lin,et al.  Characterizing exhaled airflow from breathing and talking. , 2010, Indoor air.

[12]  Student Member Ashrae,et al.  Air distribution effectiveness with stratified air distribution systems , 2009 .

[13]  P V Nielsen,et al.  Dispersion of exhaled droplet nuclei in a two-bed hospital ward with three different ventilation systems. , 2006, Indoor air.

[14]  David L Powers,et al.  Boundary Value Problems and Partial Differential Equations Ed. 6 , 2009 .

[15]  P V Nielsen,et al.  Dispersal of exhaled air and personal exposure in displacement ventilated rooms. , 2002, Indoor air.

[16]  Vice President,et al.  AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR CONDITIONING ENGINEERS INC. , 2007 .

[17]  R G Sextro,et al.  Pollutant dispersion in a large indoor space: Part 1 -- Scaled experiments using a water-filled model with occupants and furniture. , 2004, Indoor air.

[18]  E. A. Hathway,et al.  The ventilation of multiple-bed hospital wards: review and analysis. , 2008, American journal of infection control.

[19]  Qingyan Chen,et al.  Experimental Study on Displacement and Mixing Ventilation Systems for a Patient Ward , 2009 .

[20]  Stephane B. Poussou Experimental investigation of airborne contaminant transport by a human wake moving in a ventilated aircraft cabin , 2008 .