Motor bearing failure from VFD induced shaft to ground voltages in HVAC applications

Investigation into fan motor bearing failures on HVAC air handlers, used to recirculate air within computer manufacturing clean rooms, has made it clear that these failures were caused by electric discharge current problems within the bearings when the motor was operated from a PWM inverter source. This is a newly identified mode of failure in this application; and as such, appears to be not fully understood by the manufacturers of the drives and motors. Although first noticed in clean room rahs, there may be greater implications for HVAC designs and other industrial applications employing VFDs. This paper discusses efforts to discover the source of this failure, measurement techniques utilized, and proposed solutions for mitigation related to this application.

[1]  W. R. Finley,et al.  Trouble shooting motor problems , 1993, Industry Applications Society 40th Annual Petroleum and Chemical Industry Conference.

[2]  T.F. Lowery,et al.  More application considerations for PWM inverter-fed low-voltage induction motors , 1993, Conference Record of 1993 Annual Pulp and Paper Industry Technical Conference.

[3]  J. Erdman,et al.  Effect of PWM inverters on AC motor bearing currents and shaft voltages , 1996 .

[4]  Thomas A. Lipo,et al.  Source of induction motor bearing currents caused by PWM inverters , 1996 .

[5]  T.F. Lowery,et al.  Application considerations for PWM inverter-fed low-voltage induction motors , 1992, [1992] Record of Conference Papers Industry Applications Society 39th Annual Petroleum and Chemical Industry Conference.

[6]  R. W. Jones,et al.  Investigation and results of eddy currents on DC motor bearings , 1990, Annual Technical Conference on Pulp and Paper Industry.