A Robust Dlqg Controller for Damping of Sub-synchronous Oscillations in a Series Compensated Power System

This paper investigates the use of Discrete Linear Quadratic Gaussian (DLQG) Compensator to damp sub synchronous oscillations in a Thyrisor Controlled Series Capacitor (TCSC) compensated power system. The study is conducted on IEEE First Benchmark Model (FBM) in which, TCSC is modelled as a discrete linear time-invariant modular unit in the synchronously rotating DQ reference frame. This modular TCSC is then integrated with the Linear Time Invariant (LTI) model of the rest of the system. The design of DLQG includes the design of a Kalman filter for full state estimation and a full state feedback for control. Since the order of the controller is as large as the order of the system considered here(27 states), the practical implementation of the controller is difficult. Hence by using Hankels norm approximation technique, the order of the controller is reduced from 27 to 15 without losing the significant system dynamics. The eigen analysis of the system shows that the use of DLQG can damp torsional oscillations as well as the swing mode oscillations simultaneously, which is practically difficult for a conventional sub-synchronous damping controller. The performance of the system with DLQG is appreciable for all operating conditions and it shows the robustness of the controller.

[1]  A.M. Kulkarni,et al.  Analysis of SSR Performance of TCSC Control Schemes Using a Modular High Bandwidth Discrete-Time Dynamic Model , 2009, IEEE Transactions on Power Systems.

[2]  S. Henschel,et al.  A discrete state-space model for SSR stabilizing controller design for TCSC compensated systems , 2005, IEEE Transactions on Power Delivery.

[3]  B.K. Keshavan,et al.  Damping of subsynchronous oscillations using STATCOM - a FACTS controller , 2004, 2004 International Conference on Power System Technology, 2004. PowerCon 2004..

[4]  Joe H. Chow,et al.  Concepts for design of FACTS controllers to damp power swings , 1995 .

[5]  A.M. Kulkarni,et al.  Discrete-Time Dynamic Model of NGH Damper , 2007, IEEE Transactions on Power Systems.

[6]  Narain Hingorani A New Scheie for Subsynchronous Resonance Damping of Torsional Oscillations and Transient Torque - Part I , 1981, IEEE Transactions on Power Apparatus and Systems.

[7]  Joe H. Chow,et al.  Robust redesign of power system damping controllers , 1995, IEEE Trans. Control. Syst. Technol..

[8]  Ian Dobson,et al.  Dynamic response of a thyristor controlled switched capacitor , 1994 .

[9]  C. F. Chen Model reduction of multivariable control systems by means of matrix continued fractions , 1974 .

[10]  G. Stein,et al.  The LQG/LTR procedure for multivariable feedback control design , 1987 .

[11]  Arindam Ghosh,et al.  Robust control of SSSC to improve torsional damping , 2001, 2001 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.01CH37194).

[12]  Joe H. Chow,et al.  Robust redesign of power system damping controllers , 1993, Proceedings of 32nd IEEE Conference on Decision and Control.

[13]  Terms, Definitions and Symbols for Subsynchronous Oscillations , 1985, IEEE Transactions on Power Apparatus and Systems.

[14]  Tae Hyun Kim,et al.  An LQG based PSS design for controlling the SSR in power systems with series-compensated lines , 1996 .

[15]  C. F. Chen,et al.  Model reduction of multivariable control systems by means of matrix continued fractions , 1972 .

[16]  Paul M. Anderson,et al.  Subsynchronous resonance in power systems , 1989 .

[17]  D.N. Walker,et al.  Torsional Vibration and Fatigue of Turbine-Generator shafts , 1981, IEEE Transactions on Power Apparatus and Systems.

[18]  Y. H. Ku,et al.  Electric Power System Dynamics , 1983 .

[19]  D.A. Hodges,et al.  Results of subsynchronous resonance test at Mohave , 1975, IEEE Transactions on Power Apparatus and Systems.

[20]  Joe H. Chow,et al.  A robust frequency domain optimization technique for tuning series compensation damping controllers , 1995 .