UNLABELLED
This article presents findings of the thermal comfort study in hospitals. A field survey was conducted to investigate the temperature range for thermal comfort in hospitals in the tropics. Thermal acceptability assessment was conducted to examine whether the hospitals in the tropics met the ASHRAE Standard-55 80% acceptability criteria. A total of 114 occupants in four hospitals were involved in the study. The results of the field study revealed that only 44% of the examined locations met the comfort criteria specified in ASHRAE Standard 55. The survey also examined the predicted percentage of dissatisfied in the hospitals. The results showed that 49% of the occupants were satisfied with the thermal environments in the hospitals. The field survey analysis revealed that the neutral temperature for Malaysian hospitals was 26.4 degrees C. The comfort temperature range that satisfied 90% of the occupants in the space was in the range of 25.3-28.2 degrees C. The results from the field study suggested that a higher comfort temperature was required for Malaysians in hospital environments compared with the temperature criteria specified in ASHRAE Standard (2003). In addition, the significant deviation between actual mean vote and predicted mean vote (PMV) strongly implied that PMV could not be applied without errors in hospitals in the tropics.
PRACTICAL IMPLICATIONS
The new findings on thermal comfort temperature range in hospitals in the tropics could be used as an important guide for building services engineers and researchers who are intending to minimize energy usage in heating, ventilating and air conditioning systems in hospitals operating in the tropics with acceptable thermal comfort level and to improve the performance and well-being of its workers.
[1]
Chungyoon Chun,et al.
Thermal comfort in Japanese schools
,
2003
.
[2]
R. Dear,et al.
Thermal adaptation in the built environment: a literature review
,
1998
.
[3]
S. A. Al-Sanea,et al.
Optimized monthly-fixed thermostat-setting scheme for maximum energy-savings and thermal comfort in air-conditioned spaces
,
2008
.
[4]
A. Nazari.
Interaction between thermal comfort and HVAC energy consumption in commercial buildings
,
2008
.
[5]
Ruey Lung Hwang,et al.
Patient thermal comfort requirement for hospital environments in Taiwan
,
2007
.
[6]
Jerald D. Parker,et al.
Heating, Ventilating, and Air Conditioning: Analysis and Design
,
1977
.
[7]
van J Joost Hoof,et al.
Forty years of Fanger’s model of thermal comfort: comfort for all?
,
2008
.