A novel virtual impedance method for droop controlled parallel UPS inverters with wireless control

This paper proposes a novel virtual impedance method for uninterruptible power system (UPS) inverters with parallel connected capability. To achieve wireless control, the droop control method is adopted. However, the power sharing accuracy is highly sensitive to the output impedance of inverter. So, a virtual output impedance is usually added to alleviate the unbalance of output impedance between each inverter and then, improve power sharing accuracy. The virtual impedance is implemented as the time derivative of the inverter output current, the differential progress will amplify the noise presented in output current, result in high sensitivity to the noise for the virtual impedance. To solve this problem, a novel virtual impedance by combining with a low-pass filter is proposed, which not only balances the output impedance of inverter, but also achieves better output voltage THD when sharing nonlinear loads. The double loop control method for inverter provids a good tracking of output voltage reference and high quality output waveform. Simulation results are presented from a parallel connected UPS system to validate this method.

[1]  Mehdi Savaghebi,et al.  Secondary Control Scheme for Voltage Unbalance Compensation in an Islanded Droop-Controlled Microgrid , 2012, IEEE Transactions on Smart Grid.

[2]  E Serban,et al.  A Control Strategy for a Distributed Power Generation Microgrid Application With Voltage- and Current-Controlled Source Converter , 2010, IEEE Transactions on Power Electronics.

[3]  Josep M. Guerrero,et al.  Wireless-control strategy for parallel operation of distributed generation inverters , 2006, Proceedings of the IEEE International Symposium on Industrial Electronics, 2005. ISIE 2005..

[4]  Yao Zhang,et al.  Theoretical and Experimental Investigation of Networked Control for Parallel Operation of Inverters , 2012, IEEE Transactions on Industrial Electronics.

[5]  J. Miret,et al.  Decentralized Control for Parallel Operation of Distributed Generation Inverters Using Resistive Output Impedance , 2005, IEEE Transactions on Industrial Electronics.

[6]  D De,et al.  Decentralized Parallel Operation of Inverters Sharing Unbalanced and Nonlinear Loads , 2010, IEEE Transactions on Power Electronics.

[7]  F. Blaabjerg,et al.  An islanding microgrid reactive power sharing scheme enhanced by programmed virtual impedances , 2012, 2012 3rd IEEE International Symposium on Power Electronics for Distributed Generation Systems (PEDG).

[8]  Luis Antonio Aguirre,et al.  UPS Parallel Balanced Operation Without Explicit Estimation of Reactive Power—A Simpler Scheme , 2008, IEEE Transactions on Circuits and Systems II: Express Briefs.

[9]  Yun Wei Li,et al.  Analysis, Design, and Implementation of Virtual Impedance for Power Electronics Interfaced Distributed Generation , 2011, IEEE Transactions on Industry Applications.

[10]  Yun Wei Li,et al.  Generalized Closed-Loop Control Schemes with Embedded Virtual Impedances for Voltage Source Converters with LC or LCL Filters , 2012, IEEE Transactions on Power Electronics.

[11]  M Castilla,et al.  Virtual Impedance Loop for Droop-Controlled Single-Phase Parallel Inverters Using a Second-Order General-Integrator Scheme , 2010, IEEE Transactions on Power Electronics.