Rejuvenation of Retired Power Cables by Heat Treatment: Experimental Simulation in Lab

In this work, heat treatment was performed on three retired 110 kV AC cables with service years of 0, 15 and 30, and the effects on the thermal and electrical performance of the cable insulation were investigated. First, each cable with a length approximately of 5 m was prepared and cut into five equal segments. Four segments of each cable were annealed at a temperature of 90, 95, 100, or 105 °C by building a small circuit to simulate cable operation. Then, a section at the middle of each segment was cut out, and the insulation layer was peeled away. The peeled-off layers from the inner, middle and outer positions were selected as the test samples. Subsequently, Fourier transform infrared spectrometry (FTIR), and differential scanning calorimetry (DSC) were performed, and the DC conduction current and dielectric breakdown strength were measured. The best thermal properties of the highest melting point, crystallinity, and smallest melting range were found when the cables were annealed at 100, 105, and 105 °C for the inner, middle, and outer positions, respectively. The highest dielectric breakdown strength and lowest electrical conductivity were found at temperatures of 95 or 100 °C for the inner and middle positions, respectively, and at 105 °C for the outer position. The FTIR results showed that thermal annealing for hundreds of hours did not adversely affect the molecular chains. It is found that this type of heat treatment could be a feasible method to rejuvenate retired cables, and a conservative temperature of 95 °C is regarded as the optimum annealing temperature.

[1]  Yoshimichi Ohki,et al.  Rejuvenation of retired power cables by heat treatment , 2019, IEEE Transactions on Dielectrics and Electrical Insulation.

[2]  G. Mazzanti,et al.  Analysis of the Combined Effects of Load Cycling, Thermal Transients, and Electrothermal Stress on Life Expectancy of High-Voltage AC Cables , 2007, IEEE Transactions on Power Delivery.

[3]  Y. Murata,et al.  DC conduction and electrical breakdown of MgO/LDPE nanocomposite , 2007, 2007 Annual Report - Conference on Electrical Insulation and Dielectric Phenomena.

[4]  G. Chen,et al.  Heat treatment of cross-linked polyethylene and its effect on morphology and space charge evolution , 2005, IEEE Transactions on Dielectrics and Electrical Insulation.

[5]  W. Zenger,et al.  Service aged 69 and 115 kV XLPE cables , 1999 .

[6]  V. G. Baranov,et al.  The melting temperature range of polymers , 1976 .

[7]  Chen Changlong Diagnosis of XLPE Cable Insulation Using Velocity of Electromagnetic Wave , 2011 .

[8]  Pierre J. Carreau,et al.  The impact of new crystalline lamellae formation during annealing on the properties of polypropylene based films and membranes , 2014 .

[9]  Hans Edin,et al.  Effect of heat-treatment and sample preparation on physical properties of XLPE DC cable insulation material , 2016, IEEE Transactions on Dielectrics and Electrical Insulation.

[10]  Leni Akcelrud,et al.  FTIR characterization of aged XLPE , 2006 .

[11]  Didac Ferrer-Balas,et al.  Influence of annealing on the microstructural, tensile and fracture properties of polypropylene films , 2001 .

[12]  Bernhard Wunderlich,et al.  Thermal Analysis of Polymeric Materials , 2022 .

[13]  Qiang Fu,et al.  Effect of annealing on the microstructure and mechanical properties of polypropylene with oriented shish-kebab structure , 2012 .

[14]  G. Teyssedre,et al.  Electrical, microstructural, physical and chemical characterization of HV XLPE cable peelings for an electrical aging diagnostic data base , 2003 .

[15]  Dali Gao,et al.  Effect of annealing on microstructure and tensile properties of polypropylene cast film , 2017, Colloid and Polymer Science.

[16]  D. Bassett,et al.  On the formation of extended‐chain lamellae in polyethylene , 1969 .

[17]  Tatsuki Okamoto,et al.  The influence of morphology on electrical tree initiation in the polyethylene under AC and impulse voltages , 1988, Proceedings., Second International Conference on Properties and Applications of Dielectric Materials.

[18]  Jianying Li,et al.  Physicochemical origin of space charge dynamics for aged XLPE cable insulation , 2014, IEEE Transactions on Dielectrics and Electrical Insulation.

[19]  N. Shimizu,et al.  Diagnosis of the aged XLPE cable using frequency and temperature characteristics of tan /spl delta/ II , 1988, Proceedings of the Twenty-First Symposium on Electrical Insulating Materials.

[20]  Qiang Zheng,et al.  Influence of annealing on conduction of high‐density polyethylene/carbon black composite , 2007 .

[21]  Yoshimichi Ohki,et al.  Dielectric breakdown of new type polymerized polyethylene using a single-site catalyst , 1999 .

[22]  Tingxi Sun,et al.  Investigation on insulation material morphological structure of 110 and 220 kV XLPE retired cables for reusing , 2014, IEEE Transactions on Dielectrics and Electrical Insulation.

[23]  Yifeng Zhao,et al.  Annealing Effects on XLPE Insulation of Retired High-Voltage Cable , 2019, IEEE Access.

[24]  E. Gulski,et al.  Advanced partial discharge diagnostic of MV power cable system using oscillating wave test system , 2000 .

[25]  F. Aras,et al.  Aging of 154 kV underground power cable insulation under combined thermal and electrical stresses , 2007, IEEE Electrical Insulation Magazine.