General Public Exposure by ELF Fields of 150–36/11-kV Substations in Urban Environment

Electromagnetic exposure of the general public due to large substations transforming voltages of 150 and 36 kV to 11 kV is investigated and safety distances for these substations have been determined. In total, 142 field measurements were executed for two substations: 91 measurements of the magnetic field and 51 measurements of the electric field. Measured momentary magnetic-field values are within the range of 0.051 to 13.17 muT. The levels of the electric field are within the range of 0.095 to 270.0 V/m. The cumulative distribution function of the measured magnetic-field values has been determined, and it is shown that the fields excellently follow a lognormal distribution. The maximal magnetic- and electric-field values for all the investigated substations are below 100 muT (values over a day and year) and 5 kV/m, respectively. When comparing the average exposure with the value of 0.4 muT, safety distances of maximally 8.1 m (average day) and 7.1 m (average year) are obtained.

[1]  K Jokela,et al.  Restricting exposure to pulsed and broadband magnetic fields. , 2000, Health physics.

[2]  Noriyuki Hayashi,et al.  Analysis of 60 Hz magnetic fields near ground level in 187 kV switchyard of a 187/66 kV AC substation , 1992 .

[3]  A.S. Safigianni,et al.  Measurements of electric and magnetic fields due to the operation of indoor power distribution substations , 2005, IEEE Transactions on Power Delivery.

[4]  T. Keikko,et al.  Electric and magnetic fields from electric power systems in living and work environment , 1999 .

[5]  Luc Martens,et al.  MEASUREMENTS OF ELF ELECTROMAGNETIC EXPOSURE OF THE GENERAL PUBLIC FROM BELGIAN POWER DISTRIBUTION SUBSTATIONS , 2008, Health physics.

[6]  John H. Dunlap,et al.  Magnetic Fields Remote from Substations , 1989, IEEE Power Engineering Review.

[7]  Guidance on determining compliance of exposure to pulsed and complex non-sinusoidal waveforms below 100 kHz with ICNIRP guidelines. , 2003, Health physics.

[8]  E Cardis,et al.  Review of the epidemiologic literature on EMF and Health. , 2001, Environmental health perspectives.

[9]  T. Keikko,et al.  Power frequency electric fields at a 400 kV substation , 1999 .

[10]  T. Keikko,et al.  Exposure to electric and magnetic fields at 110 kV gas insulated substation (GIS) , 2002, IEEE/PES Transmission and Distribution Conference and Exhibition.

[11]  A. Ahlbom Guidelines for limiting exposure to time-varying electric, magnetic, and electromagnetic fields (up to 300 GHz) , 1998 .

[12]  T. Keikko,et al.  Comparison of electric and magnetic fields near 400 kV electric substation with exposure recommendations of the European Union , 2002, IEEE/PES Transmission and Distribution Conference and Exhibition.

[13]  M Feychting,et al.  A pooled analysis of magnetic fields and childhood leukaemia , 2000, British Journal of Cancer.

[14]  W. K. Daily,et al.  Measurements and computations of electromagnetic fields in electric power substations , 1994 .

[15]  Seppo Valkealahti,et al.  EXPOSURE TO MAGNETIC FIELD HARMONICS IN THE VICINITY OF INDOOR DISTRIBUTION SUBSTATIONS , 2006, Health physics.

[16]  M. Misakian,et al.  Measurements of power frequency magnetic fields away from power lines , 1991 .