Recloser-Fuse Coordination Assessment by Classification Technique for Distribution Systems with Distributed Generation

Abstract In this article, a novel approach is presented to study the impact of distributed generation on recloser–fuse coordination. This approach is based on the assessment of the recloser–fuse coordination due to the penetration of distributed generation with specified location and capacity for a given fault location. This assessment process acts as a classifier based on finding the operating sequence of all reclosers and fuses in the path from the faulted node to the substation. This sequence is compared with a pre-required sequence obtained from the protection coordination philosophy and then provides the distribution system operator with a result indicating whether the recloser–fuse coordination still holds or is lost. Consequently the operator can make the proper decision according to this classification process. One of the proper decisions that can be taken into account in the case of recloser–fuse miscoordination is to adapt the recloser setting such that the coordination can be re-attained. This new approach has been implemented on the IEEE 37-node test feeder using MATLAB-based developed software (The MathWorks, Natick, Massachusetts, USA), and the obtained results are presented and discussed.

[1]  N. Schulz,et al.  Unbalanced Distribution Power Flow with Distributed Generation , 2006, 2005/2006 IEEE/PES Transmission and Distribution Conference and Exhibition.

[2]  P.P. Barker,et al.  Determining the impact of distributed generation on power systems. I. Radial distribution systems , 2000, 2000 Power Engineering Society Summer Meeting (Cat. No.00CH37134).

[3]  James S. Thorp,et al.  Power System Protection , 2000 .

[4]  K.L. Butler-Purry,et al.  Impact of Distributed Generation on the IEEE 34 Node Radial Test Feeder with Overcurrent Protection , 2007, 2007 39th North American Power Symposium.

[5]  S.M.T. Bathaee,et al.  Maintaining The Recloser-Fuse Coordination in Distribution Systems in Presence of DG by Determining DG's Size , 2008 .

[6]  A. Yokoyama,et al.  Prevention of Reliability Degradation from Recloser–Fuse Miscoordination Due To Distributed Generation , 2008, IEEE Transactions on Power Delivery.

[7]  Magdy M. A. Salama,et al.  Distributed generation technologies, definitions and benefits , 2004 .

[8]  W. H. Kersting,et al.  Radial distribution test feeders , 1991, 2001 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.01CH37194).

[9]  N.N. Schulz,et al.  Development of Three-Phase Unbalanced Power Flow Using PV and PQ Models for Distributed Generation and Study of the Impact of DG Models , 2007, IEEE Transactions on Power Systems.

[10]  D. Shirmohammadi,et al.  A three-phase power flow method for real-time distribution system analysis , 1995 .

[11]  W. H. Kersting Radial distribution test feeders , 1991 .

[12]  P. A. Kotos,et al.  IEEE standard inverse-time characteristic equations for overcurrent relays , 1999 .

[13]  Kimmo Kauhaniemi,et al.  Impact of distributed generation on the protection of distribution networks , 2004 .

[14]  Paul M. Anderson,et al.  Analysis of faulted power systems , 1973 .

[15]  Ying-Hong Lin,et al.  An adaptive PMU based fault detection/location technique for transmission lines. I. Theory and algorithms , 2000 .

[16]  E. J. Holmes,et al.  Protection of Electricity Distribution Networks , 1998 .

[17]  Xiaofeng Zhang,et al.  A distribution short circuit analysis approach using hybrid compensation method , 1995 .