청정공간에서 제품과 팬필터유닛의 위치에 따른 오염물질의 전파 특성

We performed a study on the contaminant transfer in a clean space for the location of product and fan filter unit using computational fluid dynamics analysis. To simplify the real product moving process, three different non-moving cases regrading the locations of product were selected: no product, at the lower side, and at the upper and lower sides. And to investigate the characteristics of the contaminant transfer, the arrangement of fan filter units was varied. Local mean air-age and contaminant distribution were used as evaluation indices. From the results, the contaminant transfer to the product was the most when the products were simultaneously located at the upper and lower sides. And the contaminant was easily exhausted regardless of the location of product when the fan filter units were properly arranged at the top side of the clean space.