Long Cable Applications From a Medium-Voltage Drives Perspective

Many installations in the petrochemical industry routinely require medium-voltage adjustable speed drives (MV ASDs) with long output cables, particularly for offshore applications and land-based well applications. This paper describes the effects of using MV ASDs with long cables. It examines the major issue known as the “standing wave effect,” which may be more prominent at certain cable lengths, as well as the design solutions to ensure proper drive and motor functionality and performance. Examples of this unique phenomenon and the effectiveness of different mitigation measures are presented using simulations and actual data. Simulations are also used to provide a comparison of operating waveforms with two- and multilevel converters. This paper recommends considerations for the installation and/or design of the MV ASD that can be implemented to avoid problems.

[1]  J. Pontt,et al.  Resonances and overvoltages in a medium voltage fan motor drive with long cables in an underground mine , 2004, Conference Record of the 2004 IEEE Industry Applications Conference, 2004. 39th IAS Annual Meeting..

[2]  T. Henriksen,et al.  Converter-fed subsea motor drives , 1996 .

[3]  S. J. Merhej,et al.  Harmonic filtering for the offshore industry , 1992, [1992] Record of Conference Papers Industry Applications Society 39th Annual Petroleum and Chemical Industry Conference.

[4]  P. W. Hammond,et al.  A new approach to enhance power quality for medium voltage AC drives , 1997 .

[5]  P. W. Hammond A new approach to enhance power quality for medium voltage drives , 1995, Industry Applications Society 42nd Annual Petroleum and Chemical Industry Conference.

[6]  Richard H. Osman,et al.  A medium-voltage drive utilizing series-cell multilevel topology for outstanding power quality , 1999, Conference Record of the 1999 IEEE Industry Applications Conference. Thirty-Forth IAS Annual Meeting (Cat. No.99CH36370).