Experimental performance analysis and modelling of liquid desiccant cooling systems for air conditioning in residential buildings

Abstract The paper presents a new desiccant cooling cycle to be integrated in residential mechanical ventilation systems. The process shifts the air treatment completely to the return air side, so that the supply air can be cooled by a heat exchanger. Purely sensible cooling is an essential requirement for residential buildings with no maintenance guarantee for supply air humidifiers. As the cooling power is generated on the exhaust air side, the dehumidification process needs to be highly efficient to provide low supply air temperatures. Solid rotating desiccant wheels have been experimentally compared with liquid sorption systems using contact matrix absorbers and cross flow heat exchangers. The best dehumidification performance at no temperature increase was obtained in an evaporatively cooled heat exchanger with sprayed lithium chloride solution. Up to 7 g kg −1 dehumidification could be reached in an isothermal process, although the surface wetting of the first prototype was low. The process then provides inlet air conditions below 20 °C for the summer design conditions of 32 °C, 40% relative humidity. With air volume flow rates of 200 m 3  h −1 the system can provide 886 W of cooling power. A theoretical model for both the contact absorber and the cross flow system has been developed and validated against experimental data for a wide range of operating conditions. A simulation study identified the optimisation potential of the system, if for example the surface wetting of the liquid desiccant can be improved.

[1]  S. K. Chaudhari,et al.  Thermodynamic Properties of Aqueous Solutions of Lithium Chloride , 2002 .

[2]  Wasim Saman,et al.  An experimental study of a cross-flow type plate heat exchanger for dehumidification/cooling , 2002 .

[3]  John R. Howell,et al.  Numerical and experimental results for coupled heat and mass transfer between a desiccant film and air in cross-flow , 1994 .

[4]  U. Eiden W. Kast: Adsorption aus der Gasphase, Ingenieurwissenschaftliche Grundlagen und technische Verfahren, VCH Verlagsgesellschaft, Weinheim, Basel, Cambridge, New York 1988. 279 Seiten, Preis: DM 220,00 , 1990 .

[5]  Terry G. Lenz,et al.  Dimensionless mass-transfer correlations for packed-bed liquid-desiccant contactors , 1996 .

[6]  Manuel R. Conde,et al.  Properties of aqueous solutions of lithium and calcium chlorides: formulations for use in air conditioning equipment design , 2004 .

[7]  Moustafa M. Elsayed,et al.  A numerical solution for cooling and dehumidification of air by a falling desiccant film in parallel flow , 1998 .

[8]  D. Y. Goswami,et al.  A review of liquid desiccant cooling , 1998 .

[9]  D. Y. Goswami,et al.  Experimental Study of the Heat and Mass Transfer in a Packed Bed Liquid Desiccant Air Dehumidifier , 1998 .

[10]  Ursula Eicker,et al.  Solar technologies for buildings , 2003 .

[11]  E. Hering,et al.  Physik für Ingenieure , 1997 .

[12]  Wasim Saman,et al.  Modelling and performance analysis of a cross-flow type plate heat exchanger for dehumidification/cooling , 2001 .