A Capacitance Bridge Method for Measuring Integrated Corona-Charge Transfer and Power Loss per Cycle

A more sensitive and accurate circuit has been devised and tested for showing integrated corona charge transfer per cycle in insulation samples. The method can be used as a very accurate and more rapid quality-control measurement of degree of impregnation or residual voids in apparatus insulation. A rather precise measurement of the fraction of gas space to solid in insulation structures can be obtained from this technique. The estimate of internal voids obtained from this technique is believed to be more accurate than that obtained from highvoltage Schering bridge measurements, with which it can be correlated.

[1]  Vladimir Karapetoff Corona Ellipses , 1929, Transactions of the American Institute of Electrical Engineers.

[2]  W. L. Lloyd,et al.  Methods Used in Investigating Corona Loss By Means of the Cathode Ray Oscillograph , 1927, Transactions of the American Institute of Electrical Engineers.

[3]  H. S. Dixon Rapid determination of corona loss from voltage-charge diagrams , 1959, Transactions of the American Institute of Electrical Engineers, Part I: Communication and Electronics.

[4]  Thomas W. Dakin,et al.  The Relation of Capacitance Increase with High Voltages to Internal Electric Discharges and Discharging Void Volume , 1958, Transactions of the American Institute of Electrical Engineers Part III Power Apparatus and Systems.