Frequency Response Analysis to recognize inductance variation in transformer due to internal short circuit

Transformer diagnosis methods have been introduced and employed to recognize transformer internal defects since many years ago. In terms of mechanical defects in transformers, turn to turn and disc to disc short circuits in transformer windings are considered as one of the main problems in transformer active part. On the other hand, Frequency Response Analysis (FRA) is considered as a robust, sensitive and high accurate method to identify transformer mechanical defects. This study has concentrated on self-inductance variation recognition due to an internal short circuit in transformer using FRA signature. A single phase 11/0.25 kV, 25 kVA transformer has been taken as test object. Frequency response of the test object was recorded for open circuit and short circuit situations. Frequency response alteration in low frequencies caused by short circuit is interpreted through mathematical calculations. Frequency response trace deviation is employed to recognize self-inductance changes due to the internal short circuit.

[1]  Mehdi Bagheri,et al.  A case study on FRA capability in detection of mechanical defects within a 400MVA transformer , 2012 .

[2]  Z.D. Wang,et al.  Investigations on sensitivity of FRA technique in diagnosis of transformer winding deformations , 2004, Conference Record of the 2004 IEEE International Symposium on Electrical Insulation.

[3]  A.J. Vandermaar,et al.  Improved detection of power transformer winding movement by extending the FRA high frequency range , 2005, IEEE Transactions on Power Delivery.

[4]  M. Bagheri,et al.  Impulse voltage distribution in intershield disk winding VS interleaved and continuous disk winding in power transformer , 2008, 2008 IEEE 2nd International Power and Energy Conference.

[5]  Daming Zhang,et al.  Transformer Frequency Response Analysis: A mathematical approach to interpret mid-frequency oscillations , 2012, 2012 IEEE International Conference on Power and Energy (PECon).

[6]  Enrique E. Mombello,et al.  Sweep frequency response analysis (SFRA) for the assessment of winding displacements and deformation in power transformers , 2008 .

[7]  Marek Florkowski,et al.  Exploitation stresses and challenges in diagnostics of electrical industrial equipment , 2011, 2011 IEEE International Symposium on Industrial Electronics.

[8]  M. S. Naderi,et al.  FRA vs. short circuit impedance measurement in detection of mechanical defects within large power transformer , 2012, 2012 IEEE International Symposium on Electrical Insulation.

[9]  A. Hekmati,et al.  Influence of Electrostatic Shielding of Disc Winding on Increasing the Series Capacitance in Transformer , 2007, 2007 IEEE Lausanne Power Tech.

[10]  M. S. Naderi,et al.  Advanced transformer winding deformation diagnosis: moving from off-line to on-line , 2012, IEEE Transactions on Dielectrics and Electrical Insulation.

[11]  M. Florkowski,et al.  Identification of winding faults in electric machines using a high frequency method , 2007, 2007 IEEE International Electric Machines & Drives Conference.

[12]  N. Abeywickrama,et al.  Effect of Core Magnetization on Frequency Response Analysis (FRA) of Power Transformers , 2008, IEEE Transactions on Power Delivery.

[13]  M. S. Naderi,et al.  Dean-Stark vs FDS and KFT methods in moisture content recognition of transformers , 2012, 2012 IEEE International Conference on Power and Energy (PECon).

[14]  M. S. Naderi,et al.  Bushing characteristic impacts on on-line Frequency Response Analysis of transformer winding , 2012, 2012 IEEE International Conference on Power and Energy (PECon).

[15]  A.J. Vandermaar,et al.  Transformer winding movement monitoring in service - key factors affecting FRA measurements , 2004, IEEE Electrical Insulation Magazine.

[16]  Syed Islam Detection of shorted turns and winding movements in large power transformers using frequency response analysis , 2000, 2000 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.00CH37077).

[17]  E.P. Dick,et al.  Transformer Diagnostic Testing by Frequuency Response Analysis , 1978, IEEE Transactions on Power Apparatus and Systems.

[18]  Mehdi Bagheri,et al.  Practical challenges in online transformer winding deformation diagnostics , 2011, 2011 2nd International Conference on Electric Power and Energy Conversion Systems (EPECS).