Simulation study on the operating characteristics of the heat pipe for combined evaporative cooling of computer room air-conditioning system

In order to improve the energy efficiency of air conditioning systems in computer rooms, this paper proposed a new concept of integrating evaporative cooling air-conditioning system with heat pipes. Based on a computer room in Shenyang, China, a mathematical model was built to perform transient simulations of the new system. The annual dynamical performance of the new system was then compared with a typical conventional computer room air-conditioning system. The result showed that the new integrated air-conditioning system had better energy efficiency, i.e. 31.31% reduction in energy consumption and 29.49% increase in COP (coefficient of performance), due to the adoption of evaporative condenser and the separate type heat pipe technology. Further study also revealed that the incorporated heat pipes enabled a 36.88% of decrease in the operation duration of the vapor compressor, and a 53.86% of reduction for the activation times of the compressor, which could lead to a longer lifespan of the compressor. The new integrated evaporative cooling air-conditioning system was also tested in different climate regions. It showed that the energy saving of the new system was greatly affected by climate, and it had the best effect in cold and dry regions like Shenyang with up to 31.31% energy saving. In some warm and humid climate regions like Guangzhou, the energy saving could be achieved up to 13.66%.

[1]  Bahgat Sammakia,et al.  Airflow and temperature distribution optimization in data centers using artificial neural networks , 2013 .

[2]  Ting Ma,et al.  Recent development and application of several high-efficiency surface heat exchangers for energy conversion and utilization , 2014 .

[3]  Shiming Deng,et al.  Multivariable control of indoor air temperature and humidity in a direct expansion (DX) air conditioning (A/C) system , 2009 .

[4]  Zhen Li,et al.  Modelling and applications of annual energy-using simulation module of separated heat pipe heat exchanger , 2013 .

[5]  Yat Huang Yau,et al.  A review on the application of horizontal heat pipe heat exchangers in air conditioning systems in the tropics , 2010 .

[6]  M. Shah A general correlation for heat transfer during film condensation inside pipes , 1979 .

[7]  Jinkyun Cho,et al.  Measurements and predictions of the air distribution systems in high compute density (Internet) data centers , 2009 .

[8]  Hiroshi Endo,et al.  Effect of climatic conditions on energy consumption in direct fresh-air container data centers , 2015, Sustain. Comput. Informatics Syst..

[9]  Ian W. Eames,et al.  Modelling thermostatic expansion valves , 2014 .

[10]  Yunting Ge,et al.  Performance simulation of refrigerated display cabinets operating with refrigerants R22 and R404A , 2008 .

[11]  Kuppan Thulukkanam Heat Exchanger Design Handbook , 2013 .

[12]  C. K. Rice The effect of void fraction correlation and heat flux assumption on refrigerant charge inventory predictions , 1987 .

[13]  Yong Chan Kim,et al.  Effects of accumulator heat exchangers on the performance of a refrigeration system , 2007 .

[14]  Xiaodong Qian,et al.  A thermal environmental analysis method for data centers , 2013 .

[15]  Hoon Kang,et al.  Performance optimization of a hybrid cooler combining vapor compression and natural circulation cycles , 2009 .

[16]  Baolong Wang,et al.  Development of an integrated air conditioner with thermosyphon and the application in mobile phone base station , 2013 .

[17]  Martin Becker Heat Transfer: A Modern Approach , 1986 .

[18]  Bijan Samali,et al.  A comparative study on the effect of different strategies for energy saving of air-cooled vapor compression air conditioning systems , 2014 .

[19]  Yong Chan Kim,et al.  Experimental Study on a Novel Hybrid Cooler for the Cooling of Telecommunication Equipments , 2006 .

[20]  Stanislaw Kajl,et al.  A comparative performance study of a direct expansion geothermal evaporator using R410A and R407C as refrigerant alternatives to R22 , 2015 .

[21]  Yat Huang Yau,et al.  The application of heat pipe heat exchangers to improve the air quality and reduce the energy consumption of the air conditioning system in a hospital ward—A full year model simulation , 2011 .

[22]  Shuangfeng Wang,et al.  Cycle performance of air conditioning system based on finned tube heat exchangers with different helix angles , 2015 .

[23]  Suhas V. Patankar,et al.  Airflow distribution through perforated tiles in raised-floor data centers , 2006 .

[24]  Yat Huang Yau,et al.  The use of a double heat pipe heat exchanger system for reducing energy consumption of treating ventilation air in an operating theatre—A full year energy consumption model simulation , 2008 .