Generalization of the delta-differential autotransformer for 12 and 18-pulse converters

This work proposes a methodology to generalize the Delta-connections for 12 and 18-pulse autotransformers. A single mathematical expression, obtained through simple trigonometric operations, represents all the connections. The proposed methodology allows choosing any ratio between the input and the output voltages. The converters can operate either as step-up or as step-down voltage. To simplify the design of the windings, graphics are generated to calculate the turn-ratio and the polarity of each secondary winding, with respect to the primary winding. A design example, followed by digital simulations, and experimental results illustrate the presented steps. The results also show that high power factor is an inherent characteristic of multi-pulse converters, without any active or passive power factor pre-regulators needs

[1]  Johannes Schaefer,et al.  Rectifier circuits : theory and design , 1965 .

[2]  I. Barbi,et al.  A 12 kW three-phase low THD rectifier with high-frequency isolation and regulated DC output , 2004, IEEE Transactions on Power Electronics.

[3]  D. A. Paice,et al.  Power Electronics Converter Harmonics , 1995 .

[4]  Shashi B. Dewan,et al.  Power Semiconductor Drives , 1984 .

[5]  F.J.M. de Seixas,et al.  A new three-phase low THD power supply with high-frequency isolation and 60V/200A regulated DC output , 2001, 2001 IEEE 32nd Annual Power Electronics Specialists Conference (IEEE Cat. No.01CH37230).

[6]  I. Barbi,et al.  A new 12 kW three-phase impulse high power factor AC-DC converter with regulated output voltage for rectifier units , 1999, 21st International Telecommunications Energy Conference. INTELEC '99 (Cat. No.99CH37007).