제습시스템이 결합된 바닥복사냉방의 제어에 관한 연구

This study has been conducted to evaluate the control performance of radiant floor cooling integrated with a dehumidification system in terms of room air temperature stability and the degree of change in the control variables in the dehumidification process. The results are as follows. First, radiant floor cooling integrated with dehumidification system shows stable room air temperature control under the sensible and latent load conditions in experimental settings. Second, there is no discomfort from the vertical temperature distribution in that the maximum difference between the heights of the ankle and the head is about 3℃. Finally, the humidity sensor can be located with the current thermostat in that there are small differences in absolute humidity in the vertical direction.