Whole building energy simulation and energy saving potential analysis of a large public building
暂无分享,去创建一个
This article explores how to use EnergyPlus to construct models to accurately simulate complex building systems as well as the inter-relationships among sub-systems such as heating, ventilation and air conditioning (HVAC), lighting and service hot water systems. The energy consumption and cost of a large public building are simulated and calculated for Leadership in Energy and Environmental Design (LEED) certification using EnergyPlus. American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) baseline model is constructed according to ASHRAE 90.1 standard and the comparison of annual energy consumption between ASHRAE baseline model and proposed model is carried out. Moreover, an energy efficiency (EE) model is built based on the design model. Meanwhile, other energy conservation measures (ECMs) such as daylighting dimming and occupant sensors are considered. The simulation results show 4.7% electricity consumption decrease but 6.9% gas consumption increase of the EE model compared to ASHRAE baseline model. In summary, the annual energy cost of the EE model is reduced by 7.75%.
[1] P. A. Torcellini,et al. Simulating Tall Buildings Using EnergyPlus , 2005 .
[2] Daniel E. Fisher,et al. EnergyPlus: creating a new-generation building energy simulation program , 2001 .
[3] Jon Hand,et al. CONTRASTING THE CAPABILITIES OF BUILDING ENERGY PERFORMANCE SIMULATION PROGRAMS , 2008 .
[4] P. Torcellini,et al. Energy Design Analysis and Evaluation of a Proposed Air Rescue and Fire Fighting Administration Building for Teterboro Airport , 2003 .