Comparison of load inverter topologies in a bipolar LVDC-distribution

Low voltage direct current (LVDC) distribution is a new low voltage distribution concept. Potential inverter topologies for a bipolar LVDC 1500 V distribution system are compared. Twoor three-level single-phase half or full bridges or three-phase load inverters can be used in LVDC distribution. Inverters can be connected to 750 V DC or 1500 V DC. The bases of comparison are the size of required LC-filters, voltage and current stresses of the components, capability to operate with reduced DC voltage and feed half-wave rectifying load. Two different LC-filter design methods are used. According to the simulation results, the most suitable singlephase load inverter topologies connected to 750 V DC are twoand three-level full bridges. The structure of three-level inverters is more complex, but the size of the required passive filter components is just half of the size of the components with twolevel inverters. The difference between LC-filter sizes is not so significant when comparing with two-and three-level inverters connected to 1500 V DC. The maximum voltage stresses of the IGBTcomponents are udc/2 in three-level inverters but udc in two-level inverters. Smaller voltage stresses are a remarkable advantage especially at higher voltage levels.

[1]  S. Bernet,et al.  A comparison of three-level converters versus two-level converters for low-voltage drives, traction, and utility applications , 2005, IEEE Transactions on Industry Applications.

[2]  H. Kakigano,et al.  DC Voltage Control of the DC Micro-grid for Super High Quality Distribution , 2007, 2007 Power Conversion Conference - Nagoya.

[3]  Tero Kaipia,et al.  An LVDC distribution system concept , 2008 .

[4]  Heung-Geun Kim,et al.  LCL-filter design for grid-connected PCS using total harmonic distortion and ripple attenuation factor , 2010 .

[5]  Zhihong Ye,et al.  Output filter design for a grid-interconnected three-phase inverter , 2003, IEEE 34th Annual Conference on Power Electronics Specialist, 2003. PESC '03..

[6]  Enrico Tironi,et al.  LV DC distribution network with distributed energy resources: Analysis of possible structures , 2005 .

[7]  M. Liserre,et al.  Design and control of an LCL-filter based three-phase active rectifier , 2001, Conference Record of the 2001 IEEE Industry Applications Conference. 36th IAS Annual Meeting (Cat. No.01CH37248).