Experiments and Fragility Analyses of Piping Systems Connected by Grooved Fit Joints With Large Deformability

The pipes with diameter of 150mm, also called DN150, are often connected by grooved fit joints and employed as the stem pipelines, which are used to transport water vertically to different building stories and distribute it horizontally to different rooms. A large deformability is often required for the grooved fit joints to accommodate the deformation concentrated between adjacent stories during an earthquake. To this end, the grooved fit joint is often improved with a wider groove to achieve such a large deformability. However, its seismic performance has not been thoroughly studied yet. This study conducted quasi-static tests on twelve DN150 grooved fit joints, including four elbow joints and eight DN150-DN80 Tee joints. The mechanical behavior, rotational capacity and failure mode were examined and discussed. The test results indicate that the fracture of the grooved fitting and the pull-out of pipes from the grooved fitting are the major damage patterns at deformations larger than 0.1rad. At small deformations less than 0.06 rad, although slight abrasion and wear were observed on the contact surface between the galvanized steel pipe and the grooved fitting, they would not result in significant leakage. Three damage states are defined accordingly and the fragility models are developed for different grooved fit joints based on test results. Finally, seismic fragility analysis of DN150 stem pipeline system in a 10-story building was conducted. It is demonstrated that the improved joints survive under the maximum credible earthquake and the leakage is highly unlikely to occur.

[1]  Chen Qiao-sheng,et al.  A Brief Introduction of FEMA P695—Quantification of Building Seismic Performance Factors , 2013 .

[2]  Hongyu Deng,et al.  Development and Contrast of Bottom Frame Structure in China's Code for Seismic Design of Buildings , 2019, E3S Web of Conferences.

[3]  Arash E. Zaghi,et al.  Seismic Fragility Study of Displacement Demand on Fire Sprinkler Piping Systems , 2014 .

[4]  Bu Seog Ju Seismic Fragility of Piping System. , 2011 .

[5]  Giuseppe Maddaloni,et al.  Seismic response evaluation of medical gas and fire-protection pipelines’ Tee-Joints , 2018 .

[6]  Andre Filiatrault,et al.  Analytical Seismic Fragility Analyses of Fire Sprinkler Piping Systems with Threaded Joints , 2015 .

[7]  Gilberto Mosqueda,et al.  Performance of Nonstructural Components during the 27 February 2010 Chile Earthquake , 2012 .

[8]  Andre Filiatrault,et al.  Seismic response of viscously damped braced thin-wall piping system: a proof-of-concept case study , 2018, Bulletin of Earthquake Engineering.

[9]  Jochen Carl,et al.  Seismic Performance of Chlorinated Polyvinyl Chloride Sprinkler Pipes , 2018, Earthquake Spectra.

[10]  Patrick Paultre,et al.  Fragility curves of typical as-built highway bridges in eastern Canada , 2012 .

[11]  Andre Filiatrault,et al.  Seismic Response of Pressurized Fire Sprinkler Piping Systems I: Experimental Study , 2015 .

[12]  P. Zavattieri,et al.  Tips and tricks for characterizing shape memory wire part 5: Full-field strain measurement by digital image correlation , 2013, Experimental Techniques.

[13]  F. Filippou,et al.  Nonlinear Analysis of Prestressed Concrete Structures , 1994 .

[14]  M. Menegotto Method of Analysis for Cyclically Loaded R. C. Plane Frames Including Changes in Geometry and Non-Elastic Behavior of Elements under Combined Normal Force and Bending , 1973 .

[15]  Qingxue Shang,et al.  Seismic fragility of flexible pipeline connections in a base isolated medical building , 2019, Earthquake Engineering and Engineering Vibration.

[16]  Stefano Pampanin,et al.  Seismic performance of non-structural components and contents in buildings: an overview of NZ research , 2016, Earthquake Engineering and Engineering Vibration.

[17]  J. Mander,et al.  Theoretical stress strain model for confined concrete , 1988 .

[18]  Arash E. Zaghi,et al.  Experimental and Analytical Studies of Hospital Piping Assemblies Subjected to Seismic Loading , 2012 .

[19]  Andre Filiatrault,et al.  Comprehensive Analytical Seismic Fragility of Fire Sprinkler Piping Systems 14-0002.pdf , 2014 .

[20]  Andre Filiatrault,et al.  Experimental Seismic Fragility of Pressurized Fire Suppression Sprinkler Piping Joints , 2014 .

[21]  K. Steinbrugge,et al.  Earthquakes, Volcanoes and Tsunamis: An Anatomy of Hazards , 1982 .

[22]  Andre Filiatrault,et al.  Performance-based seismic design of nonstructural building components: The next frontier of earthquake engineering , 2014, Earthquake Engineering and Engineering Vibration.

[23]  Quanwang Li,et al.  Performance evaluation and damage assessment of steel frame buildings under main shock–aftershock earthquake sequences , 2007 .

[24]  K. K. Lo,et al.  Nonstructural damage from the Northridge earthquake , 1995 .

[25]  Quanwang Li,et al.  Damage inspection and vulnerability analysis of existing buildings with steel moment-resisting frames , 2008 .

[26]  Cheng Yu Wu,et al.  The seismic response , 1996 .

[27]  Andre Filiatrault,et al.  Seismic Fragility Study of Fire Sprinkler Piping Systems with Grooved Fit Joints , 2015 .

[28]  Robert E. Bachman,et al.  Creating Fragility Functions for Performance-Based Earthquake Engineering , 2007 .

[29]  Philip D. LeGrone AN ANALYSIS OF FIRE SPRINKLER SYSTEM FAILURES DURING THE NORTHRIDGE EARTHQUAKE AND COMPARISON WITH THE SEISMIC DESIGN STANDARD FOR THESE SYSTEMS , 2002 .