A series compensator with fault current limiting function

A method to control a power converter-based series compensator (SC) such that it can also function as a fault current limiter (FCL) is described. The SC achieves the current limiting function through the magnitude and phase control of its injection voltage. By such action, it is shown that the FCL will absorb energy from the external network. The consequence is an increase in the voltage across the terminals of the SC energy storage system. A method to size the storage system is then described. By incorporating the energy storage system with the proposed control scheme to realize the injection voltage, it is seen that the FCL is also effective in improving the supply quality of the power system.

[1]  H.-W. Neumuller,et al.  Resistive current limiters with YBCO films , 1997, IEEE Transactions on Applied Superconductivity.

[2]  S. W. Middlekauff,et al.  System and customer impact: considerations for series custom power devices , 1998 .

[3]  D. M. Vilathgamuwa,et al.  Design and Analysis of the Inverter-Side Filter Used in the Dynamic Voltage Restorer , 2002, IEEE Power Engineering Review.

[4]  Liangzhen Lin,et al.  Application studies of superconducting fault current limiters in electric power systems , 2002 .

[5]  Shigeyuki Sugimoto,et al.  Principle and characteristics of a fault current limiter with series compensation , 1996 .

[6]  San Shing Choi,et al.  Dynamic voltage restoration with minimum energy injection , 2000, 2000 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.00CH37077).

[7]  M. Steurer,et al.  A Novel Hybrid Current-Limiting Circuit Breaker for Medium Voltage: Principle and Test Results , 2002, IEEE Power Engineering Review.

[8]  K. Frohlich,et al.  A novel hybrid current-limiting circuit breaker for medium voltage: principle and test results , 2003, 2003 IEEE Power Engineering Society General Meeting (IEEE Cat. No.03CH37491).

[9]  San Shing Choi,et al.  Performance improvement of the dynamic voltage restorer with closed-loop load voltage and current-mode control , 2002 .

[10]  Narain G. Hingorani,et al.  Introducing custom power , 1995 .

[11]  San Shing Choi,et al.  Dynamic voltage restoration with minimum energy injection , 2000 .

[12]  L. Morgan,et al.  Experience with an inverter-based dynamic voltage restorer , 1999 .