Experiments during flow boiling of a R22 drop-in: R422D adiabatic pressure gradients

Abstract R22, the HCFC most widely used in refrigeration and air-conditioning systems in the last years, is phasing-out. R422D, a zero ozone-depleting mixture of R125, R134a and R600a (65.1%/31.5%/3.4% by weight, respectively), has been recently proposed as a drop-in substitute. For energy consumption calculations and temperature control, it is of primary importance to estimate operating conditions after substitution. To determine pressure drop in the evaporator and piping line to the compressor, in this paper the experimental adiabatic pressure gradients during flow boiling of R422D are reported for a circular smooth horizontal tube (3.00 mm inner radius) in a range of operating conditions of interest for dry-expansion evaporators. The data are used to establish the best predictive method for calculations and its accuracy: the Moreno-Quiben and Thome method provided the best predictions for the whole database and also for the segregated data in the annular flow regime. Finally, the experimental data have been compared with the adiabatic pressure gradients of both R22 and its much used alternative R407C available in the literature.

[1]  J. Thome,et al.  Investigation of Flow Boiling in Horizontal Tubes: Part I, A New Diabatic Two-Phase Flow Pattern Map , 2005 .

[2]  J. Thome,et al.  Flow pattern based two-phase frictional pressure drop model for horizontal tubes, Part II: New phenomenological model , 2007 .

[3]  A. Greco,et al.  Convective boiling of pure and mixed refrigerants: An experimental study of the major parameters affecting heat transfer , 2008 .

[4]  R. Lockhart Proposed Correlation of Data for Isothermal Two-Phase, Two-Component Flow in Pipes , 1949 .

[5]  Alberto Cavallini,et al.  Working fluids for mechanical refrigeration — Invited paper presented at the 19th International Congress of Refrigeration, The Hague, August 1995 , 1996 .

[6]  Rita Mastrullo,et al.  An evaluation of R22 substitutes performances regulating continuously the compressor refrigeration capacity , 2004 .

[7]  R. Radermacher,et al.  Prediction of Pressure Drop during Horizontal Annular Flow Boiling of Pure and Mixed Refrigerants , 1989 .

[8]  Milton L. Lee 1 – Physical and Chemical Properties , 1981 .

[9]  H. Gurney Heat Transmission , 1909, Nature.

[10]  Robert J. Moffat,et al.  Describing the Uncertainties in Experimental Results , 1988 .

[11]  H. Müller-Steinhagen,et al.  A simple friction pressure drop correlation for two-phase flow in pipes , 1986 .

[12]  J. Thome,et al.  Investigation of Flow Boiling in Horizontal Tubes: Part II, Development of a New Heat Transfer Model for Stratified-Wavy, Dryout and Mist Flow Regimes , 2005 .

[13]  J. Thome,et al.  Flow Boiling in Horizontal Tubes. Part 1; Development of a Diabatic Two–Phase Flow Pattern Map , 1998 .

[14]  R. Grundmann The Montreal protocol , 2003 .

[15]  L. Friedel Improved Friction Pressure Drop Correlation for Horizontal and Vertical Two-Phase Pipe Flow , 1979 .