Experimental determination of the optimum performance of ejector refrigeration system depending on ejector area ratio

The performance of the ejector refrigeration system using ejectors with cylindrical mixing chamber is studied at operating conditions with choking in the mixing chamber. The condenser pressure is chosen so that the secondary flow choking can occur even in the ejector with the smallest area ratio. In the present study, the performance of the constructed system is determined by using six configurations of ejector and R-123 as working fluid in the system. The study is performed over a range of the ejector area ratio from 6.5 to 11.5 at the compression ratio 2.47. In the studied range, the experimental coefficient of performance of the system rises from 0.29 to 0.41, as the optimum generator temperature increases from 83 to 103 °C. Similar results were also found in the parametric study when the efficiencies of the nozzle and diffuser are taken as 0.90.

[1]  Da-Wen Sun,et al.  Performance characteristics of HCFC-123 ejector refrigeration cycles , 1996 .

[2]  K. Cizungu,et al.  Performance comparison of vapour jet refrigeration system with environment friendly working fluids , 2001 .

[3]  Satha Aphornratana,et al.  An experimental investigation of a steam ejector refrigerator: the analysis of the pressure profile along the ejector , 2004 .

[4]  Bin-Juine Huang,et al.  Empirical correlation for ejector design , 1999 .

[5]  Bin-Juine Huang,et al.  Development of an ejector cooling system with thermal pumping effect , 2006 .

[6]  Rafet Yapici,et al.  Experimental investigation of performance of vapor ejector refrigeration system using refrigerant R123 , 2008 .

[7]  Mark Worall,et al.  An experimental investigation of steam ejectors for applications in jet-pump refrigerators powered by low-grade heat , 1999 .

[8]  J. C. Champoussin,et al.  Les paramètres géométriques optima d'un éjecto-compresseur frigorifique , 1993 .

[9]  Rafet Yapici,et al.  Performance characteristics of the ejector refrigeration system based on the constant area ejector flow model , 2005 .

[10]  A. Selvaraju,et al.  Experimental investigation on R134a vapour ejector refrigeration system , 2006 .

[11]  Bin-Juine Huang,et al.  A 1-D analysis of ejector performance , 1999 .

[12]  Vojislav Kecman,et al.  Modelling of vapour-compression liquid chillers with neural networks , 2001 .

[13]  Ian W. Eames,et al.  A new prescription for the design of supersonic jet-pumps: the constant rate of momentum change method , 2002 .

[14]  Yuan-Jen Chang,et al.  Enhancement of a steam-jet refrigerator using a novel application of the petal nozzle , 2000 .