Evaluation of delaminated high-voltage rotating machine stator winding groundwall insulation

In recent years, a distinctive nonlinear characteristic of the current versus ramped dc voltage test response has been observed which identifies rotating machines having delaminated stator winding insulation. This characteristic response is described and analyzed. Two illustrative examples of hydroelectric generators with delaminated groundwall insulation are presented. In one case, the ramped voltage test curve is compared against power factor and capacitance versus ac voltage measurements taken on the aged stator winding and on unused spare coils. Results of dissection analyses of aged stator coils removed from the winding and spare coils are also discussed. In the second example, ramped voltage test data are compared to on-line partial discharge measurements.

[1]  W. McDermid,et al.  Significance of defects found during high direct-voltage ramp tests , 1999, Proceedings: Electrical Insulation Conference and Electrical Manufacturing and Coil Winding Conference (Cat. No.99CH37035).

[2]  L. M. Rux,et al.  High-voltage DC tests for evaluating stator winding insulation: uniform step, graded step, and ramped test methods , 1997, IEEE 1997 Annual Report Conference on Electrical Insulation and Dielectric Phenomena.

[3]  S. Grzybowski,et al.  Detecting delaminated stator winding insulation using the ramped high-voltage DC test method , 1999 .