Measurement and Simulation of Induced Voltage and Current on 110 KV Crossing Transmission Lines under UHV AC Transmission Lines

The induced electricity of 110 kV transmission lines which cross the UHV AC transmission lines may threaten personal safety of the maintenance staff. In this paper, field measurement of the induced voltage and induced current on a 110 kV crossing line inside Jinhua in Zhejiang province is performed. The electrostatic induced voltage on the measured line is 12.24 kV. The power frequency electromagnetic field simulation model is established, and the calculation results are consistent with the measured. Influence factors analysis shows that the electrostatic induced voltage on the 110 kV line is 12.78 kV, the electromagnetic induced voltage is 12.3 V, the induced current through ground wire is less than 1A when the UHV lines operate at full load. The induced voltage and current decrease while the crossing distance increases. Parallel lines induction is much higher than crossing lines. The electromagnetic induced voltage after ground knife-switch shut down would exceed the human safety voltage 36 V while the crossing angle is less than 30?, so the temporary ground wire must be hanged to ensure safety of the maintenance staff.

[1]  M.M. Abdel-Salam,et al.  Induced voltages on fence wires and pipe lines by AC power transmission lines , 1992, Conference Record of the 1992 IEEE Industry Applications Society Annual Meeting.

[2]  G. L. Wilson,et al.  Electrostatically Induced Voltages and Currents on Conducting Objects under EHV Transmission Lines , 1971 .

[3]  张占龙,et al.  Optimization Algorithm forArranging Extra-and Ultra-high Transmission Lines Subjected to the Constraintsof Power Frequency Electromagnetic Environment Condition , 2015 .

[4]  Li Zhenqian,et al.  Induced Voltage and Induced Current on AC Same-tower Four-circuit Lines Comprised of Double-circuit 1 000kV Lines and Double-circuit 500kV or 220kV Lines , 2013 .

[5]  Liu Zhen-ya,et al.  Innovation of UHVAC Transmission Technology in China , 2013 .

[6]  Zhou Hao,et al.  Calculation and Analysis on Induced Voltage and Current of 1 000 kV Transmission Line Adopting Structure of Double Circuit on the Same Tower , 2011 .

[7]  L. Ye Accurate Calculation of Three-dimensional Power Frequency Electromagnetic Field for Space Crossed Transmission Line , 2011 .

[8]  Pei Chun-ming Calculation Method of Electric Field Intensity for AC Crossing Transmission Lines , 2011 .

[9]  Chai Ya-jing,et al.  Calculation of Inductive Voltage and Current for 500 kV Double Circuits Transmission Lines on Single Tower , 2008 .

[10]  Y Shu,et al.  Research of Key Technologies for UHV Transmission , 2007 .

[11]  Kun-Mu Chen,et al.  Steady-state and shock currents induced by ELF electric fields in a human body and a nearby vehicle , 1990 .