Offline to online mechanical deformation diagnosis for power transformers

Internal winding deformations of power transformers can be detected using the conventional offline frequency response analysis (FRA) which is a well-known and widely accepted tool for the detection of winding and core deformations. In addition of being offline technique, interpretation of FRA signature is based on graphical analysis that requires skilled personnel as there is no reliable standard code for FRA signature identification and quantification. This paper presents the possibility of using an alternative online technique based on construction a voltage-current (ΔV-I) locus of the operating transformer and considering it as a reference signature. In order to fully explore the performance and reliability of the new proposed approach particularly for real-life distribution transformers, the paper investigates and compares the performance of the proposed and the FRA approaches for disk space variation and axial displacement faults. The transformer distributed parameter model is used to simulate FRA signatures while a detailed three-dimensional finite element model is used to generate the ΔV-I louses for healthy and faulty operating conditions. Simulation results are compared to highlight the advantages and limitations of the two internal fault detection strategies.

[1]  Sang-Yong Jung,et al.  Finite-Element Analysis of Short-Circuit Electromagnetic Force in Power Transformer , 2011, IEEE Transactions on Industry Applications.

[2]  A. Abu-Siada,et al.  Understanding power transformer frequency response analysis signatures , 2013, IEEE Electrical Insulation Magazine.

[3]  D.M. Sofian,et al.  Interpretation of Transformer FRA Responses— Part I: Influence of Winding Structure , 2009, IEEE Transactions on Power Delivery.

[4]  A. Abu-Siada,et al.  A Novel Online Technique to Detect Power Transformer Winding Faults , 2012, IEEE Transactions on Power Delivery.

[5]  N. Abeywickrama,et al.  Effect of Core Magnetization on Frequency Response Analysis (FRA) of Power Transformers , 2008, IEEE Transactions on Power Delivery.

[6]  Q. H. Wu,et al.  Transformer winding condition assessment using frequency response analysis and evidential reasoning , 2010 .

[7]  N. Abeywickrama,et al.  High-Frequency Modeling of Power Transformers for Use in Frequency Response Analysis (FRA) , 2008, IEEE Transactions on Power Delivery.

[8]  Stefan Tenbohlen,et al.  Experimental and theoretical investigation of disc space variation in real high-voltage windings using transfer function method , 2010 .

[9]  H. Herman,et al.  Non-destructive measurement of the degradation of transformer insulating paper , 2006, IEEE Transactions on Dielectrics and Electrical Insulation.

[10]  M. Sabahi,et al.  Finite element analyses of short circuit forces in power transformers with asymmetric conditions , 2008, 2008 IEEE International Symposium on Industrial Electronics.

[11]  Mehdi Vakilian,et al.  Transformer winding diagnosis using comparison of transfer function coefficients , 2011, The 8th Electrical Engineering/ Electronics, Computer, Telecommunications and Information Technology (ECTI) Association of Thailand - Conference 2011.

[12]  Mehdi Bagheri,et al.  Practical challenges in online transformer winding deformation diagnostics , 2011, 2011 2nd International Conference on Electric Power and Energy Conversion Systems (EPECS).

[13]  Stefan Tenbohlen,et al.  Mathematical Comparison Methods to Assess Transfer Functions of Transformers to Detect Different Types of Mechanical Faults , 2010, IEEE Transactions on Power Delivery.