A tube-by-tube reduction method for simultaneous heat and mass transfer characteristics for plain fin-and-tube heat exchangers in dehumidifying conditions

This study proposed a new method, namely a tube-by-tube reduction method to analyze the performance of fin-and-tube heat exchangers having plain fin configuration under dehumidifying conditions. The mass transfer coefficients which seldom reported in the open literature, are also presented. For fully wet conditions, it is found that the reduced results for both sensible heat transfer performance and the mass transfer performance by the present method are insensitive to change of inlet humidity. Unlike those tested in fully dry condition, the sensible heat transfer performance under dehumidification is comparatively independent of fin pitch. The ratio of the heat transfer characteristic to mass transfer characteristic (hc,o/hd,oCp,a) is in the range of 0.6~1.0, and the ratio is insensitive to change of fin spacing at low Reynolds number. However, a slight drop of the ratio of (hc,o/hd,oCp,a) is seen with the decrease of fin spacing when the Reynolds number is sufficient high. This is associated with the more pronounced influence due to condensate removal by the vapor shear. Correlations are proposed to describe the heat and mass performance for the present plate fin configurations. These correlations can describe 89% of the Chilton Colburn j-factor of the heat transfer (jh) within 15% and can correlate 81% of the Chilton Colburn j-factor of the mass transfer (jm) within 20%.

[1]  Chi-Chuan Wang,et al.  Sensible heat and friction characteristics of plate fin-and-tube heat exchangers having plane fins , 1996 .

[2]  V. Gnielinski New equations for heat and mass transfer in turbulent pipe and channel flow , 1976 .

[3]  Chi-Chuan Wang,et al.  Heat transfer and friction correlation for compact louvered fin-and-tube heat exchangers , 1999 .

[4]  S. Ramadhyani,et al.  Prediction of cooling-coil performance under condensing conditions , 1993 .

[5]  Chi-Chuan Wang,et al.  Heat transfer and friction characteristics of plain fin-and-tube heat exchangers, part I: new experimental data , 2000 .

[6]  Chi-Chuan Wang,et al.  Performance of plate finned tube heat exchangers under dehumidifying conditions , 1997 .

[7]  S. Ramadhyani,et al.  CORRELATIONS FOR PREDICTING THE AIR-SIDE NUSSELT NUMBERS AND FRICTION FACTORS IN CHILLED-WATER COOLING COILS , 1994 .

[8]  Robert J. Moffat,et al.  Describing the Uncertainties in Experimental Results , 1988 .

[9]  K. Ogawa,et al.  Heat and Mass Transfer Performances on Plate Fin and Tube Heat Exchangers under Dehumidification , 1988 .

[10]  J. W. Ramsey,et al.  Thermal Environmental Engineering , 1970 .

[11]  T. R. Bump AVERAGE TEMPERATURES IN SIMPLE HEAT EXCHANGERS , 1963 .

[12]  Chi-Chuan Wang,et al.  An experimental study of the airside performance of the superslit fin-and-tube heat exchangers , 2000 .

[13]  A. London,et al.  Compact heat exchangers , 1960 .

[14]  Ephraim M Sparrow,et al.  Transfer characteristics of two-row plate fin and tube heat exchanger configurations , 1976 .

[15]  Effect of anti-corrosion coating on the thermal characteristics of a louvered finned tube heat exchangers under dehumidifying conditions , 1995 .

[16]  R. Webb,et al.  Calculation of Fin Efficiency for Wet and Dry Fins , 1996 .

[17]  Yeon-Pun Chang,et al.  An experimental study of heat transfer and friction characteristics of typical louver fin-and-tube heat exchangers , 1998 .