Optimal power flow evaluation of distribution network capacity for the connection of distributed generation

Distributed generation capacity will increase significantly as a result of UK Government-led targets and incentives. Whereas the technical problems arising from distribution-level connections may be mitigated for individual connections, the anticipated connection volumes imply a potential risk of conflict between connections, in that inappropriately sized or located plant could constrain further development of the network and consequently threaten the achievement of renewable energy targets. One means of addressing this risk is to encourage development at sites that are more suitable and at the same time discouraging those at inappropriate ones. First of all network operators must be able to evaluate the available capacity on the system (i.e. the headroom). A technique is presented that facilitates such an analysis. Termed ‘reverse load-ability’, the approach models fixed-power factor distributed generation as negative loads and uses the optimal power flow to perform negative load shedding that effectively maximises capacity and identifies available headroom. The technique is applied to an extensive distribution and sub-transmission network. It rapidly identifies available headroom within the imposed thermal and voltage constraints. Furthermore, its use is demonstrated in examining the consequences of a sequence of connections in terms of the impact on available headroom and in sterilising the network.

[1]  Fabrizio Giulio Luca Pilo,et al.  Optimal distributed generation allocation in MV distribution networks , 2001, PICA 2001. Innovative Computing for Power - Electric Energy Meets the Market. 22nd IEEE Power Engineering Society. International Conference on Power Industry Computer Applications (Cat. No.01CH37195).

[2]  C. L. Masters Voltage rise: the big issue when connecting embedded generation to long 11 kV overhead lines , 2002 .

[3]  Kyu-Ho Kim,et al.  Dispersed generator placement using fuzzy-GA in distribution systems , 2002, IEEE Power Engineering Society Summer Meeting,.

[4]  Y. H. Song,et al.  Modern heuristics application to distribution system optimization , 2002, 2002 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.02CH37309).

[5]  K. Tomsovic,et al.  Placement of dispersed generation systems for reduced losses , 2000, Proceedings of the 33rd Annual Hawaii International Conference on System Sciences.

[6]  J.W. Bialek,et al.  Optimal power flow as a tool for fault level-constrained network capacity analysis , 2005, IEEE Transactions on Power Systems.

[7]  N. S. Rau,et al.  Optimum location of resources in distributed planning , 1994 .

[8]  Yasuhiro Hayashi,et al.  Application of tabu search to optimal placement of distributed generators , 2001, 2001 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.01CH37194).

[9]  Francisco D. Galiana,et al.  A survey of the optimal power flow literature , 1991 .

[10]  A. R. Wallace,et al.  Planning for Optimal Accommodation of Dispersed Generation in Distribution Networks , 2003 .