The paper deals with the description and analysis of the method of the additional earthing of the affected phase used for the elimination of the fault current during an earth fault in a compensated network. The efficiency of this method is strongly influenced by the fault location and resistance and, in some cases, its application can lead to deteriorating the situation at the point of the fault and thus to increasing the risk of dangerous touch voltage. The paper analyses the results of the simulations of selected fault cases where the negative influence of the additional earthing of the affected phase on the fault current magnitude (and therefore on the occurrence of the dangerous touch voltage at the point of the fault and in the neighboring LV network) can be expected. All the theoretical conclusions and assumptions were consequently verified by experiments in a real distribution network. Their results were then used in the final part as a basis for proposing the measures to apply the method in MV distribution networks.
[1]
Petr Toman,et al.
Experimental measuring of the earth faults currents in MV compensated networks
,
2010
.
[2]
N. McDonagh,et al.
Use of Faulted Phase Earthing using a custom built earth fault controller
,
2010
.
[3]
R. Feuillet,et al.
Detection of resistive single‐phase earth faults in a compensated power‐distribution system
,
2007
.
[4]
Petr Toman.
RIPPLE CONTROL SIGNAL USING FOR EARTH FAULT LOCATION IN MV NETWORKS
,
2005
.
[5]
S. Vitet,et al.
Location strategies and evaluation of detection algorithms for earth faults in compensated MV distribution systems
,
2000
.
[6]
Matti Lehtonen,et al.
Characteristics of earth faults in electrical distribution networks with high impedance earthing
,
1998
.