직류옵셋제거필터에 의한 거리계전기법의 성능 개선에 관한 연구
暂无分享,去创建一个
Distance relay is widely used for the protection of long transmission line. Most of distance relay used to calculate line impedance by measuring voltage and current using DFT. So if there is a computation error due to the influence of phasor by DC offset component, due to excessive vibration by measuring line impedance, overreach or underreach can be occurs, and then abnormal and non-operation of distance relay can be issue. It is very important to implement the robust distance relaying that is not affected by DC offset component. This paper describes an enhanced distance relaying based on the DC offset elimination filter to minimize the effects of DC offset on a long transmission line. The proposed DC offset elimination filter has not need any prior information. The phase angle delay of the proposed DC offset filter did not occurred and the gain error was not found. The enhanced distance relay uses fault current as well as residual current. The behavior of the proposed distance relaying using off-line simulation has been verified using data about several fault conditions generated by the ATP simulation software.
[1] 이인규,et al. 하둡기반 빅데이터 시스템을 이용한 스마트그리드 전력데이터 분석 , 2015 .