Analysis of a Static Transfer Switch with Respect to Transfer Time
暂无分享,去创建一个
Thyristor-based static transfer switches (STSs) are used in uninterruptible power supply systems and in distribution networks to provide connection to alternate sources of ac power for critical loads when the main sources fail. Performance of STSs from a transfer time point of view has not been reported in the technical literature, however. This performance evaluation is a complex issue due to the dependence of the transfer time on gating scheme and commutation between thyristors. This article provides a thorough analysis of a fast gating strategy for STS systems. It derives analytical expressions to estimate the transfer time for different operating conditions and identifies the worst-case scenario(s) in which maximum transfer time occurs. The analytical results are validated based on time-domain simulation studies using the PSCAD/EMTDC package for a medium-voltage system. The simulation results are verified based on comparison with those obtained from an experimental set-up.
[1] Hossein Mokhtari,et al. High speed silicon controlled rectifier static transfer switch , 1999 .
[2] R.W. De Doncker,et al. 15 kV medium voltage static transfer switch , 1995, IAS '95. Conference Record of the 1995 IEEE Industry Applications Conference Thirtieth IAS Annual Meeting.