Modeling Chlorine Residuals in Drinking‐Water Distribution Systems
暂无分享,去创建一个
A mass‐transfer‐based model is developed for predicting chlorine decay in drinking‐water distribution networks. The model considers first‐order reactions of chlorine to occur both in the bulk flow and at the pipe wall. The overall rate of the wall reaction is a function of the rate of mass transfer of chlorine to the wall and is therefore dependent on pipe geometry and flow regime. The model can thus explain field observations that show higher chlorine decay rates associated with smaller pipe sizes and higher flow velocities. It has been incorporated into a computer program called EPANET that can perform dynamic water‐quality simulations on complex pipe networks. The model is applied to chlorine measurements taken at nine locations over 53 h from a portion of the South Central Connecticut Regional Water Authority's service area. Good agreement with observed chlorine levels is obtained at locations where the hydraulics are well characterized. The model should prove to be a valuable tool for managing chlori...
[1] Pratim Biswas,et al. A model for chlorine concentration decay in pipes , 1993 .
[2] Robert M. Clark,et al. Using Computer Models to Determine the Effect of Storage on Water Quality , 1993 .
[3] P. Boulos,et al. Discrete Volume‐Element Method for Network Water‐Quality Models , 1993 .
[4] Robert M. Clark,et al. Modeling contaminant propagation in drinking-water distribution systems , 1993 .