Striking distance factors and practical lightning rod installations: a quantitative study

Abstract This paper presents the results of a sensitivity analysis of upward leader initiation from lightning rods in response to an approaching lightning downward leader, with particular focus on rods installed on practical structures. The analysis takes into account the effect of the charge distribution on the downward leader, the criterion used to determine leader initiation, structure geometry, rod height and rod tip radius. The analysis shows that the: (i) “constant plus head” charge distribution results in smaller striking distances, particularly for larger charges or peak currents; (ii) choice of leader initiation criterion can result in significant differences in striking distance—the “critical radius” concept results in larger striking distances; (iii) structure geometry, particularly height but also the structure width and shape, are significant factors in the determination of striking distance, as is the position of the rod on the structure; and (iv) lightning rod geometry (tip radius) is an important parameter, particularly for larger rod heights. Therefore, it is suggested that any model for lightning interception must take into account both geometric and lightning parameters. The paper also makes some comparisons with the predictions of the simple Electrogeometric Model often used to determine the protection zone of lightning rods.

[1]  C. Moore,et al.  Lightning Rod Improvement Studies , 2000 .

[2]  I. Gallimberti,et al.  Theoretical modelling of the development of the positive spark in long gaps , 1994 .

[3]  F. Rizk,et al.  Modeling of lightning incidence to tall structures. I. Theory , 1994 .

[4]  M. Uman,et al.  The Lightning Discharge , 1987 .

[5]  A. Bondiou-Clergerie,et al.  A simplified model for the simulation of positive-spark development in long air gaps , 1997 .

[6]  Franco D'Alessandro The use of ‘Field Intensification Factors’ in calculations for lightning protection of structures , 2003 .

[7]  C. B. Moore,et al.  Measurements of lightning rod responses to nearby strikes , 2000 .

[8]  G. Carrara,et al.  Switching surge strength of large air gaps: A physical approach , 1976, IEEE Transactions on Power Apparatus and Systems.

[9]  E. Garbagnati,et al.  Lightning stroke simulation by means of the leader progression model. I. Description of the model and evaluation of exposure of free-standing structures , 1990 .

[10]  Gildas Hartmann,et al.  Theoretical Evaluation of Peek's Law , 1984, IEEE Transactions on Industry Applications.

[11]  I. Gallimberti,et al.  The inception phase of positive leaders in triggered lightning : comparison of modeling with experimental data , 1999 .

[12]  R. T. Waters,et al.  Determination of the striking distance of lightning to earthed structures , 1995, Proceedings of the Royal Society of London. Series A: Mathematical and Physical Sciences.

[13]  F.A.M. Rizk Modeling of lightning incidence to tall structures. II. Application , 1994 .

[14]  Franco D'Alessandro,et al.  A “Collection Volume Method” for the placement of air terminals for the protection of structures against lightning , 2001 .

[15]  A. J. Eriksson The Incidence of Lightning Strikes to Power Lines , 1987, IEEE Transactions on Power Delivery.