Empirical analysis of high pressure SF6 gas breakdown strength in a spark gap switch

It is difficult to predict or measure the breakdown strength of SF6 gas in the high pressure range. Therefore, it is hard to find reference data of the high pressure SF6 gas breakdown strength. This paper attempts to provide empirically a novel criterion for the estimation of SF6 gas breakdown strength in a spark gap switch. For this purpose, J.C. Martin's breakdown field strength of non-uniform gap in air and Kuffel et al's breakdown field strength by exploiting streamer criterion of uniform field in SF6 gas are adopted. The research is made for the empirical method of predicting the high pressure SF6 breakdown strength and compared results have been ascertained with several experimental data from different investigators in a wide range of pd (pressure times distance) and field enhancement factor (FEF). For further confirmation of the empirical approach, we have designed and developed a high pressure spark gap switch to be closely coupled to a high voltage PFN-Marx system. The designed spark gap switch operates above 1 MV. Our tests have verified the prediction of the breakdown strength of the SF6 filled spark gap switch in a pd range of 0.27-1.62 MPa . cm (2.7 to 16.2 bar.cm).

[1]  H. Rahaman,et al.  Analytical Prediction of High Pressure SF6 Gas Breakdown Strength in a Spark Gap Switch , 2008, 2008 IEEE International Power Modulators and High-Voltage Conference.

[2]  A. Pedersen,et al.  Inherent Limitations in Uniform Field Discharge Data for SF6 , 1972 .

[3]  A. H. Guenther,et al.  J. C. Martin on pulsed power , 1996 .

[4]  R. A. Hore High-voltage circuit-breakers , 1957 .

[5]  D. Mukhedkar,et al.  A New Approach to Compute Uniform Field Breakdown of Gases , 1978, IEEE Transactions on Power Apparatus and Systems.

[6]  A.E.D. Heylen,et al.  Sparking formulae for very high-voltage Paschen characteristics of gases , 2006, IEEE Electrical Insulation Magazine.

[7]  R. Garzon High Voltage Circuit Breakers : Design and Applications , 2002 .

[8]  A. Pedersen Criteria for Spark Breakdown in Sulfur Hexafluoride , 1970 .

[9]  E. Kunhardt Electrical Breakdown of Gases: The Prebreakdown Stage , 1980, IEEE Transactions on Plasma Science.

[10]  Marco S Di Capua,et al.  A simple self-breaking 2 MV gas switch , 1987 .

[11]  D.V.Razevig High voltage engineering , 2006, 2006 Eleventh International Middle East Power Systems Conference.

[12]  D.A. Goerz,et al.  A low-profile high-voltage compact gas switch , 1997, Digest of Technical Papers. 11th IEEE International Pulsed Power Conference (Cat. No.97CH36127).

[13]  J. Kuffel,et al.  High Voltage Engineering: Fundamentals , 1984 .

[14]  W. Sarjeant,et al.  High-Power Electronics , 1989 .

[15]  E. Kuffel,et al.  High voltage engineering , 2006, 2006 Eleventh International Middle East Power Systems Conference.