대지저항률의 주파수 의존성

A new method measuring soil resistivity in frequency range of 5-500[kHz] using variable frequency inverter was resented, and soil resistivity was analysed by resistive and reactive components on the basis of magnitude and phase of measured ground impedance. The test lead arrangement was proposed to reduce the inductive coupling in test circuit for measuring the soil resistivity. The frequency dependence of soil resistivity was mainly caused by the inductive current flowing though grounding conductors over the frequency of 70[kHz].