Test of anti-islanding protections according to IEC 62116: An experimental feasibility assessment

One of the main issues concerning the Inverter based Distributed Generators (DGs) is the possibility that inverters could feed parts of the public grid, even when the grid is disconnected from the main power system. Such a condition, that is called unwanted island, is potentially critical both for safety and for consumers' operations. In order to avoid unwanted islands, it's mandatory equipping the generating plant with an Interface Protection (IP) which has to detect the islanding condition and, in this case, to disconnect the generator from the public grid. Several methods for identifying island condition have been proposed, both passive and active, each one characterized by its pros and cons. The standard IEC 62116 was promulgated with the aim of regulating a test procedure to evaluate the IP effectiveness of PhotoVoltaic (PV) inverters independently from the island detection method implemented. The paper discusses the test procedure proposed by the standard IEC 62116 and presents some experimental activities developed by RSE spa, aimed at the assessment of test feasibility and effectiveness.

[1]  Zhihong Ye,et al.  Evaluation of anti-islanding schemes based on nondetection zone concept , 2003, IEEE 34th Annual Conference on Power Electronics Specialist, 2003. PESC '03..

[2]  S. P. Chowdhury,et al.  Islanding protection of active distribution networks with renewable distributed generators: A comprehensive survey , 2009 .

[3]  Saad Mekhilef,et al.  Robust hybrid anti-islanding method for inverter-based distributed generation , 2010, TENCON 2010 - 2010 IEEE Region 10 Conference.

[4]  D. Menniti,et al.  Islanding detection active methods: Implementation of simulation models using ATP-EMTP , 2010, Proceedings of 14th International Conference on Harmonics and Quality of Power - ICHQP 2010.

[5]  Fei Wang,et al.  Power Equations and Non-Detection Zone of Passive Islanding Detection and Protection Method for Grid Connected Photovoltaic Generation System , 2009, 2009 Pacific-Asia Conference on Circuits, Communications and Systems.

[6]  Dehong Xu,et al.  Analysis of the Non-detection Zone with Passive Islanding Detection Methods for Current Control DG System , 2009, 2009 Twenty-Fourth Annual IEEE Applied Power Electronics Conference and Exposition.

[7]  F. Wang,et al.  Islanding Detection Using a Coordinate Transformation Based Phase-Locked Loop , 2007, 2007 IEEE Power Electronics Specialists Conference.