Numerical simulation of horizontal spiral-coil ground source heat pump system: Sensitivity analysis and operation characteristics.

This study concerns the operation characteristics of horizontal spiral-coil ground source heat pump (GSHP) system. A numerical model is established, which takes into account the geothermal gradient, as well as the varying ambient air temperature. More importantly, a heat pump model is also included to consider dynamically-changing loads due to specific COP characteristics. The accuracy of the model is validated with experimental results in Metz’s work and the model presented by Mei. Circulating fluid temperatures are compared with and without considering the effect of heat pump COP. Influence factors affecting the operation characteristics of horizontal spiral-coil GSHP system are investigated and their influence degrees are also compared. Impacts of daily variations of thermal load and operation models on the performance of horizontal spiral-coil GSHP system are also investigated. Results show that without considering the effect of heat pump, the difference between average inlet fluid temperatures in cooling and heating models can be 4.1% and 11.5%. Among factors influencing the performance of horizontal spiral-coil GSHP system, soil thermal conductivity and pipe spacing are main factors. When analyzing the annual or average operation characteristics of horizontal GSHP system, daily variations of load can be neglected. Under the condition of equal total loads, the average performance of intermittent operation is poorer than continuous operation and day-high/night-low operation. And continuous operation has the best performance.

[1]  Guohui Gan,et al.  Prediction of the thermal performance of horizontal-coupled ground-source heat exchangers , 2011 .

[2]  Min-Jun Kim,et al.  Thermal performance evaluation and parametric study of a horizontal ground heat exchanger , 2016 .

[3]  Taeyeon Kim,et al.  Applications of building-integrated coil-type ground-coupled heat exchangers—Comparison of performances of vertical and horizontal installations , 2015 .

[4]  Jeffrey D. Spitler,et al.  Development and validation of a Slinky™ ground heat exchanger model☆ , 2015 .

[5]  Liangliang Sun,et al.  Ground source heat pump system: A review of simulation in China , 2012 .

[6]  Min-Jun Kim,et al.  A novel hybrid design algorithm for spiral coil energy piles that considers groundwater advection , 2015 .

[7]  Min-Jun Kim,et al.  Optimum design of horizontal ground-coupled heat pump systems using spiral-coil-loop heat exchangers , 2016 .

[8]  Sandip K. Saha,et al.  Numerical study of horizontal ground heat exchanger for high energy demand applications , 2015 .

[9]  Robert Charlier,et al.  Formulation of a 1D finite element of heat exchanger for accurate modelling of the grouting behaviour: Application to cyclic thermal loading , 2016 .

[10]  Hikari Fujii,et al.  NUMERICAL MODELING OF SLINKY-COIL HORIZONTAL GROUND HEAT EXCHANGERS CONSIDERING SNOW COVERAGE EFFECTS , 2013 .

[11]  Marc A. Rosen,et al.  An analytical approach to evaluating the effect of thermal interaction of geothermal heat exchangers on ground heat pump efficiency , 2014 .

[12]  Viung C. Mei,et al.  Heat transfer of buried pipe for heat pump application , 1989 .

[13]  Gianpiero Colangelo,et al.  CFD simulations of horizontal ground heat exchangers: A comparison among different configurations , 2012 .

[14]  Peter John Cleall,et al.  Factors influencing collection performance of near surface interseasonal ground energy collection and storage systems , 2016 .

[15]  Chanjuan Han,et al.  Sensitivity analysis of a vertical geothermal heat pump system , 2016 .

[16]  D. Marcotte,et al.  On the estimation of thermal resistance in borehole thermal conductivity test , 2008 .

[17]  Hongxing Yang,et al.  Study on spiral source models revealing groundwater transfusion effects on pile foundation ground heat exchangers , 2015 .

[18]  Bernard Souyri,et al.  Geothermal helical heat exchangers: Comparison and use of two-dimensional axisymmetric models , 2014 .

[19]  Michele De Carli,et al.  Design of borehole heat exchangers for ground-source heat pumps: A literature review, methodology comparison and analysis on the penalty temperature , 2012 .

[20]  Zhaohong Fang,et al.  The research on ring-coil heat transfer models of pile foundation ground heat exchangers in the case of groundwater seepage , 2014 .

[21]  Guohui Gan,et al.  Dynamic interactions between the ground heat exchanger and environments in earth–air tunnel ventilation of buildings , 2014 .

[22]  O. Kolditz,et al.  A numerical study on the sustainability and efficiency of borehole heat exchanger coupled ground source heat pump systems , 2016 .

[23]  Enzo Zanchini,et al.  Long-term performance of large borehole heat exchanger fields with unbalanced seasonal loads and groundwater flow , 2012 .

[24]  Adam Hawkes,et al.  A review of domestic heat pumps , 2012 .

[25]  Michele De Carli,et al.  Thermal performance of two types of energy foundation pile: Helical pipe and triple U-tube , 2013 .

[26]  Michele De Carli,et al.  Long-term analysis of two GSHP systems using validated numerical models and proposals to optimize the operating parameters , 2015 .

[27]  Lin Lu,et al.  Investigation on heat transfer around buried coils of pile foundation heat exchangers for ground-coupled heat pump applications , 2012 .

[28]  Yungang Wang,et al.  Modeling the interactions between the performance of ground source heat pumps and soil temperature variations , 2014 .

[29]  Weibo Yang,et al.  An in situ thermal response test for borehole heat exchangers of the ground-coupled heat pump system , 2013 .

[30]  P. D. Metz Ground-coupled heat pump system experimental results , 1983 .

[31]  Yong Li,et al.  Analysis of Geo-Temperature Restoration Performance under Intermittent Operation of Borehole Heat Exchanger Fields , 2015 .

[32]  Lin Lu,et al.  A new analytical solution for horizontal geothermal heat exchangers with vertical spiral coils , 2016 .

[33]  Frank P. Incropera,et al.  Fundamentals of Heat and Mass Transfer , 1981 .

[34]  Yi Man,et al.  Heat transfer analysis of pile geothermal heat exchangers with spiral coils , 2011 .