Controlled Large-Scale Tests of Practical Grounding Electrodes—Part II: Comparison of Analytical and Numerical Predictions With Experimental Results

This paper presents tests carried out at an outdoor experimental facility, described in the companion Part 1 paper, to investigate the performance of practical grounding systems. Here, the results of low-voltage dc, ac, and impulse tests performed on rod and grid electrodes are described, and the measured quantities are compared with computed values obtained from numerical models. Measured ground resistance and impedance at low frequency (including power frequency) showed reasonable agreement with simple standard formulae and computational models, but revealed a significant falloff with current magnitude in the range often used for practical testing of high-voltage grounding systems. This may have implications for the specifications of grounding test equipment and extrapolation of measured ground resistance/impedance at low-voltage/current to values representative of realistic fault currents. A frequency dependence of ground impedance was also measured. Specifically, a fall in impedance over a frequency range up to 100 kHz is not generally accounted for in grounding models.

[1]  P. Chowdhuri,et al.  Correlation between laboratory and field tests on the impulse impedance of rod-type ground electrodes , 2003 .

[2]  H. Griffiths,et al.  Determination of threshold electric field E/sub C/ of soil under high impulse currents , 2005, IEEE Transactions on Power Delivery.

[3]  G. R. Olhoeft,et al.  Low-frequency electrical properties. , 1985 .

[4]  M. Uematsu,et al.  Static Dielectric Constant of Water and Steam , 1980 .

[5]  A. Haddad,et al.  Controlled Large-Scale Tests of Practical Grounding Electrodes—Part I: Test Facility and Measurement of Site Parameters , 2014, IEEE Transactions on Power Delivery.

[6]  Fermín Navarrina,et al.  A boundary element numerical approach for grounding grid computation , 1999 .

[7]  M. Popov,et al.  On high-frequency circuit equivalents of a vertical ground rod , 2005, IEEE Transactions on Power Delivery.

[8]  D. Mukhedkar,et al.  Measured and Computed Current Densities in Buried Ground Conductors , 1981, IEEE Transactions on Power Apparatus and Systems.

[9]  Dinkar Mukhedkar,et al.  Substation Ground Impedance: Comparative Field Measurements with High and Low Current Injection Methods , 1984, IEEE Power Engineering Review.

[10]  L. A. Geddes,et al.  Electrical properties of metallic electrodes , 1990, Medical and Biological Engineering and Computing.

[11]  E. Sunde Earth conduction effects in transmission systems , 1949 .

[12]  S. Bourg,et al.  Deep earth electrodes in highly resistive ground: frequency behaviour , 1995, Proceedings of International Symposium on Electromagnetic Compatibility.

[13]  Noureddine Harid,et al.  Characterisation of tower base earthing systems under impulse conditions , 2004 .

[14]  Petar Sarajcev,et al.  A review of methods for grounding grid analysis , 2009, SoftCOM 2009 - 17th International Conference on Software, Telecommunications & Computer Networks.

[15]  Donald Kasten,et al.  Scale Model Studies of Station Grounding Grids , 1983, IEEE Transactions on Power Apparatus and Systems.

[16]  Leonid Grcev,et al.  An electromagnetic model for transients in grounding systems , 1990 .

[17]  Deepak Lathi,et al.  Impulse measurements in earthing systems , 2012 .

[18]  J. G. Sverak Simplified Analysis of Electrical Gradients Above a Ground Grid, Part I: How Good Is the Present IEEE Method? (A Special Report for WG78.1) , 1984, IEEE Power Engineering Review.

[19]  A. Haddad,et al.  A new frequency-dependent surge impedance calculation method for high-voltage towers , 2006, IEEE Transactions on Power Delivery.

[20]  L. S. Collett,et al.  Electrical nonlinear phenomena in rocks , 1973 .

[21]  Noureddine Harid,et al.  Proposal for measurement of earth impedance using variable frequency injection , 2010, Measurement Science and Technology.

[22]  P. Lipavsky,et al.  Measurement of Ground Potential Difference at Power Substations , 1991, IEEE Power Engineering Review.

[23]  Wallace do Couto Boaventura,et al.  Testing and evaluating grounding systems of high voltage energized substations: alternative approaches , 1999 .

[24]  S. Visacro,et al.  Response of Grounding Electrodes to Impulsive Currents: An Experimental Evaluation , 2009, IEEE Transactions on Electromagnetic Compatibility.

[25]  Kandiah Arulanandan Hydraulic and Electrical Flows in Clays , 1969 .

[26]  S Sekioka,et al.  Analytical Surveys of Transient and Frequency-Dependent Grounding Characteristics of a Wind Turbine Generator System on the Basis of Field Tests , 2010, IEEE Transactions on Power Delivery.

[27]  H. Griffiths,et al.  Performance of earthing systems of low resistivity soils , 2006, IEEE Transactions on Power Delivery.

[28]  D. Mukhedkar,et al.  Substatiion Ground Impedance: Comparative Field Measurements with High and Low Current Injection Methods , 1984, IEEE Transactions on Power Apparatus and Systems.

[29]  N.M. Nor,et al.  Characterization of ionization phenomena in soils under fast impulses , 2006, IEEE Transactions on Power Delivery.