Optimizing hybrid ventilation in public spaces of complex buildings – A case study of the Wisconsin Institutes for Discovery

Abstract Complex buildings such as hospitals and laboratories require intensive ventilation and cooling loads in order to meet operational demands. One way to reduce energy use while meeting these demanding requirements in complex buildings is the incorporation of hybrid ventilation in areas that do not require high and continuous loads such as public spaces. This research establishes an experimental approach to test and analyze various hybrid ventilation strategies in an occupied, complex building utilizing hybrid ventilation in public spaces. To optimize the use of hybrid ventilation, this research focuses on tracking three performance criteria: energy savings, occupant comfort and indoor-air quality. The framework establishes a variety of hybrid ventilation strategies to test, and outlines how to analyze results graphically and through linear regression modeling. This experimental approach is illustrated through a case study example of a laboratory building located in Madison–Wisconsin. The selection of the ideal hybrid ventilation strategy for the public space studied resulted in 56 percent average savings in ventilation and cooling load when HV is in use, and established a potential to use hybrid ventilation for 28 percent of the 111 day cooling season (20 percent savings in mechanical cooling over the summer).

[1]  Kenneth L. Gillespie,et al.  A Specifications Guide for Performance Monitoring Systems , 2007 .

[2]  Kevin J. Lomas,et al.  Exploiting a hybrid environmental design strategy in a US continental climate , 2007 .

[3]  Gail Brager,et al.  A Standard for Natural Ventilation , 2000 .

[4]  Malcolm J. Cook,et al.  Low energy architecture for a severe US climate: Design and evaluation of a hybrid ventilation strategy , 2007 .

[5]  Standard Ashrae Thermal Environmental Conditions for Human Occupancy , 1992 .

[6]  James Brodrick,et al.  Natural and Hybrid Ventilation , 2006 .

[7]  G Carrilho da Graça,et al.  Design and testing of a control strategy for a large, naturally ventilated office building , 2004 .

[8]  Koen Steemers,et al.  Space Planning and Energy Efficiency in Laboratory Buildings: The Role of Spatial, Activity and Temporal Diversity , 2007 .

[9]  End Use Annual energy review , 1984 .

[10]  Henrik Brohus,et al.  Detailed Measurements of Thermal Comfort, IAQ and Ventilation Effectiveness in a Danish Hybrid Ventilated Office Building , 2001 .

[11]  Malcolm J. Cook,et al.  Environmental performance of a naturally ventilated city centre library , 2007 .

[12]  J. E. Janssen,et al.  Ventilation for acceptable indoor air quality , 1989 .

[13]  Moncef Krarti,et al.  Assessment of natural and hybrid ventilation models in whole-building energy simulations , 2011 .

[14]  Qiang Zhang,et al.  Model-based benchmarking with application to laboratory buildings , 2002 .

[15]  Dale Sartor,et al.  Rating energy efficiency and sustainability in laboratories: Results and lessons from the Labs21 program , 2004 .