Surface Flashover Characteristics on Poor Contact in N 2 /O 2 Mixture Gas under Non-Uniform Field

This paper presents the surface flashover characteristics to simulate the poor contact between an anode and a solid dielectric in a mixture gas (8/2) under a non-uniform field. The surface flashover voltage of the mixture gas revealed the irregular tendency that was not in accordance with the Paschen's law with an increasing gap of the poor contact. In addition, the insulation performance of the mixture gas at 0.6MPa was comparable to that of gas of 0.1MPa based on the insulation performance on the poor contact. These results are able to apply the insulation design of eco-friendly gas insulation switchgear considering the internal faults.

[1]  Yoku Mukaiyama,et al.  An investigation of breakdown voltage with small arc current due to poor contact in SF/sub 6/ gas , 1992 .

[2]  M. Akazaki,et al.  Particle-Initiated Breakdown Characteristics of Conical Insulator in N2 GAS and N2/02 Mixture under DC Voltage , 1987, IEEE Transactions on Electrical Insulation.

[3]  Kwang-Sik Lee,et al.  Breakdown Characteristics of SF6 and Liquefied SF₆ at Decreased Temperature , 2012 .

[4]  Dong-Young Lim,et al.  Study on oxygen/nitrogen gas mixtures for the surface insulation performance in gas insulated switchgear , 2015, IEEE Transactions on Dielectrics and Electrical Insulation.

[5]  K. Naito,et al.  AC withstand voltage characteristics of insulator string covered with snow , 1988 .

[6]  H. Chan,et al.  Converse magnetoelectric effect in three-phase composites of piezoceramic, metal cap, and magnet , 2007 .

[7]  J. Suehiro,et al.  DC corona discharge from floating particle in low pressure SF/sub 6/ , 2006, IEEE Transactions on Dielectrics and Electrical Insulation.

[8]  Junya Suehiro,et al.  Motion behavior and deactivation method of free-conducting particle around spacer between diverging conducting plates under DC voltage in atmospheric air , 2003 .

[9]  E. Kuffel,et al.  Experimental and Analytical Studies of Factors Which Affect Flashover Voltage on Polluted Insulation Surfaces , 1974 .

[10]  Toshiaki Rokunohe,et al.  Fundamental insulation characteristics of air; N2, CO2, N2/O2, and SF6/N2 mixed gases , 2006 .

[11]  T. Takuma Discharge Characteristics of Gaseous Dielectrics , 1986, IEEE Transactions on Electrical Insulation.

[12]  Shotaro Tominaga,et al.  Influence of Arc-Decomposed SF6 Gas on Cast EPOXY Insulators for Gas Insulated Switchgears , 1979, IEEE Transactions on Power Apparatus and Systems.

[13]  Xingliang Jiang,et al.  Effect of water streams on the AC breakdown performance of short rod-plane air gaps , 2014, IEEE Transactions on Dielectrics and Electrical Insulation.

[14]  T. Oomori,et al.  Development of SF$_{6}$-Free 72.5 kV GIS , 2007, IEEE Transactions on Power Delivery.