Electrostatic hazards with underground plastic pipes at petrol stations
暂无分享,去创建一个
The paper analyses some ignition incidents that have been reported with insulating, (non-conductive) underground plastic pipes in retail petrol stations. The occurrence of the incidents is compared with voltage measurements, observations of the typical spread of streaming currents recorded in gasoline handling and theoretical estimates of the voltages on the pipes. The comparisons suggest that neither incendive sparks from unbonded conductors nor incendive brush discharges from insulating pipe surfaces can be ruled out although both are expected to be rare. The hazards can be prevented by using pipes with earthed conductive or dissipative inner linings.
[1] H. L. Walmsley. THE ELECTROSTATIC FIELDS AND POTENTIALS GENERATED BY THE FLOW OF LIQUID THROUGH PLASTIC PIPES , 1996 .
[2] G. L. Hearn,et al. Electrostatic ignition hazards arising from fuel flow in plastic pipelines , 2002 .
[3] H. L. Walmsley,et al. Electrostatic ignition hazards in road tanker loading: Part 1. Review and experimental measurements , 1992 .
[4] L. G. Britton,et al. Some characteristics of liquid-to-metal discharges involving a charged “low risk” oil , 1982 .