Simulation of a Clean Room Fire II. Needs of Smoke Control System and Springkler System

Numerical simulations were carried out for a fire in a clean room to confirm needs of a smoke control system and a sprinkler system, and to investigate a possible smoke spread-out. For a 1 MW methanol fire in a space of floor and 4 m high, smoke spread-out was scrutinized for failure of the sprinkler system and/or the smoke control system. It was shown that the smoke control system removes smoke safely without the sprinkler system and that the sprinkler system is required to suppress smoke generation and spread of the fire, and to remove the smoke quickly. It was also confirmed that highly reliable sprinkler heads and automatic fire detection system are required for the sprinkler and smoke control systems.