Flammable liquid storage tanks could collapse easily and cause the accident spread rapidly in the high-temperature environment of pool fire, because pressure in the tank rises and the yield strength of wall decrease.So it is great significance to study the development of wall material under high temperature for the safety of flammable liquids tank farm. Taking 1,2- dichloropropane storage tank for example, based on the methods of heat transfer and numerical simulation, the mathematical model for thermal response of wall material 16MnR steel is builded to analyse the mechanical response of 16MnR steel under pool fire. When a pool fire of single tank took place in tank farm, the 1,2-dichloropropane was heated and gasitied that cause pressurizing, while the mechanical property of 16MnR steel weakened. By the finished model, this paper calculated the fail time of wall is 28.6min;failpoint of pressure is 2.065MPa;failpoint of temperature is 245°C,while temperature on heating surface of wall is 700-800 °C
[1]
Wensheng Lin,et al.
Experimental studies on the thermal stratification and its influence on BLEVEs
,
2010
.
[2]
A. M. Birk,et al.
Liquid temperature stratification and its effect on BLEVEs and their hazards
,
1996
.
[3]
A. M. Birk.
Scale effects with fire exposure of pressure-liquefied gas tanks
,
1995
.
[4]
A. M. Birk,et al.
On the response of 500 gal propane tanks to a 25% engulfing fire
,
2006
.
[5]
P. K. Ramskill.
A description of the “engulf” computer codes - codes to model the thermal response of an LPG tank either fully or partially engulfed by fire
,
1988
.
[6]
Antonio C. M. Sousa,et al.
Thermal response analysis of LPG tanks exposed to fire
,
1988
.