Design and Analysis on the Turn-to-Turn Fault Protection Scheme for the Control Winding of a Magnetically Controlled Shunt Reactor

AC overvoltage emerges on dc buses of a magnetically controlled shunt reactor when a turn-to-turn fault occurs within the control winding (CtrW). Overvoltage protections are thus employed. However, this paper addresses a problem in the application of overvoltage protection against CtrW turn-to-turn faults where such a protective scheme may operate in an unacceptable time delay or even malfunction in some fault cases. It is shown that the ac overvoltage on dc buses during a turn-to-turn fault tends to be intermittent voltage spikes rather than standard sinusoidal waveform, and the fault feature may even not exist in some cases. The cause of the problem is investigated in this paper by dividing the operating state for the excitation system into three stages. It is proved that the appearance of overvoltage on dc buses is dependent on zero-crossing of the total control current. Simulation results and physical model tests have demonstrated the theoretical analysis in this paper. Moreover, a new protective scheme that is capable of detecting a 2% CtrW turn-to-turn fault by using the fundamental component in the total control current is proposed.

[2]  J. Vitins,et al.  Protection of thyristors against overvoltage with breakover diodes , 1988 .

[3]  Wei Xu,et al.  The simulation of the controllable reactor and it's application in Ultra High Voltage Transmission Lines , 2011, 2011 International Conference on Advanced Power System Automation and Protection.

[4]  T. Zheng,et al.  Microprocessor-based protection scheme for high-voltage magnetically controlled shunt reactors , 2014 .

[5]  Mingxing Tian,et al.  A controllable reactor of transformer type , 2004, IEEE Transactions on Power Delivery.

[6]  P. B. Winston,et al.  Static VAr compensator protection , 1995 .

[7]  Jianchao Zheng,et al.  A new multi-gap spark switch connected with frequency-dependent network for EHV overvoltage protection applications , 2012, IEEE Transactions on Dielectrics and Electrical Insulation.

[8]  S.V. Smolovik,et al.  Steady-state and transient stability of 500 kV long-distance AC transmission lines with magnetically controlled shunt reactors , 2005, 2005 IEEE Russia Power Tech.

[9]  Igor Ivanković,et al.  Sensitive turn fault protection for power transformer , 2005 .

[10]  G. Trudel,et al.  A 735 kV shunt reactors automatic switching system for Hydro-Quebec network , 1996 .

[11]  E. W. Kimbark Suppression of Ground-Fault Arcs on Single-Pole-Switched EHV Lines by Shunt Reactors , 1964 .

[12]  Yan Xie,et al.  Applied research on controllable shunt reactor in Ultra-High Voltage ac transmission system , 2008, 2008 International Conference on Electrical Machines and Systems.

[13]  R. R. Karymov,et al.  Comparison of magnetically controlled reactor (MCR) and thyristor controlled reactor (TCR) from harmonics point of view , 2006 .

[14]  Qiu Yu-feng Modeling of Extra-high Voltage Magnetically Controlled Shunt Reactor , 2008 .

[15]  Igor Ivanković,et al.  Sensitive turn to turn fault protection for power transformer , 2006 .

[16]  Baichao Chen,et al.  Modeling and characteristics research on EHV magnetically controlled reactor , 2007, 2007 International Power Engineering Conference (IPEC 2007).

[17]  Yaozhong Liu,et al.  Modeling and Harmonic Optimization of a Two-Stage Saturable Magnetically Controlled Reactor for an Arc Suppression Coil , 2012, IEEE Transactions on Industrial Electronics.