Optimization of mechanical draft counter flow wet-cooling towers using a rigorous model

In this paper, an optimal design algorithm for mechanical draft counter flow wet-cooling towers based on the rigorous Poppe model and mixed-integer nonlinear programming (MINLP) is presented. Unlike the widely used Merkel method, the Poppe model takes into consideration the effects of the water loss by evaporation and the nonunity of the Lewis factor. As a result, the Poppe model is able to predict the performance of wet-cooling towers very accurately compared to the Merkel method. The optimization problem is formulated as an MINLP model by considering all the mass and energy balances, equations for physical properties, and empirical correlations for the loss and overall mass transfer coefficients in the packing region of the tower, in addition to feasibility constraints. The objective function to be minimized is the total annual cost, which includes capital and operating costs. The mathematical programming problem is solved with the GAMS software. Six case studies are used to show the application of the proposed algorithm. The case studies demonstrate that there can be large differences between the optimal designs based on the Poppe method and the Merkel method.

[1]  Ralph L. Webb,et al.  Design of Cooling Towers by the Effectiveness-NTU Method , 1989 .

[2]  Detlev G. Kröger,et al.  Loss coefficient correlation for wet-cooling tower fills , 2003 .

[3]  K. W. Li,et al.  Power Plant System Design , 1985 .

[4]  Detlev G. Kro¨ger,et al.  Cooling tower performance evaluation: Merkel, Poppe, and e-NTU methods of analysis , 2005 .

[5]  Mehmet Sait Söylemez,et al.  ON THE OPTIMUM SIZING OF COOLING TOWERS , 2001 .

[6]  Aldo R. Vecchietti,et al.  Modeling of discrete/continuous optimization problems: characterization and formulation of disjunctions and their relaxations , 2003, Comput. Chem. Eng..

[7]  Mehmet Sait Söylemez,et al.  On the optimum performance of forced draft counter flow cooling towers , 2004 .

[8]  Chengqin Ren,et al.  An Analytical Approach to the Heat and Mass Transfer Processes in Counterflow Cooling Towers , 2006 .

[9]  Detlev G. Kröger,et al.  Refinement of the Transfer Characteristic Correlation of Wet-Cooling Tower Fills , 2005 .

[10]  Chengqin Ren,et al.  Corrections to the simple effectiveness-NTU method for counterflow cooling towers and packed bed liquid desiccant–air contact systems , 2008 .

[11]  J. S. Schliesing,et al.  Extending Cooling Tower thermal Performance Prediction Using a Liquid-Side Film Resistance Model , 1991 .

[12]  F. N Kemmer,et al.  Nalco water handbook , 1979 .

[13]  James M. Douglas,et al.  Conceptual Design of Chemical Processes , 1988 .

[14]  Michael Kintner-Meyer,et al.  Cost-optimal design for cooling towers , 1995 .

[15]  J. C. Kloppers,et al.  The Lewis factor and its influence on the performance prediction of wet-cooling towers , 2005 .

[16]  Arturo Jiménez-Gutiérrez,et al.  A Disjunctive Programming Model for Simultaneous Synthesis and Detailed Design of Cooling Networks , 2009 .

[17]  Arturo Jiménez-Gutiérrez,et al.  MINLP optimization of mechanical draft counter flow wet-cooling towers , 2010 .

[18]  A. F. Mills Basic Heat and Mass Transfer , 1999 .

[19]  Arturo Jiménez-Gutiérrez,et al.  MINLP synthesis of optimal cooling networks , 2007 .

[20]  P. J. Banks,et al.  A General Theory of Wet Surface Heat Exchangers and its Application to Regenerative Evaporative Cooling , 1981 .

[21]  Mahmoud M. El-Halwagi,et al.  Water Integration of Eco-Industrial Parks Using a Global Optimization Approach , 2010 .

[22]  D. G. Kröger,et al.  Air-cooled heat exchangers and cooling towers , 2005 .

[23]  Eusiel Rubio-Castro,et al.  Optimal design of effluent-cooling systems using a mathematical programming model , 2010 .

[24]  J. W. Sutherland,et al.  Analysis of Mechanical-Draught Counterflow Air/Water Cooling Towers , 1983 .

[25]  Amir A. Al-Haddad,et al.  A Modified Analysis of Counter Flow Wet Cooling Towers , 1997 .

[26]  David Kendrick,et al.  GAMS, a user's guide , 1988, SGNM.

[27]  Fletcher Osterle,et al.  On the analysis of counter-flow cooling towers , 1991 .

[28]  Amir N. Nahavandi,et al.  The effect of evaporation losses in the analysis of counterflow cooling towers , 1975 .

[29]  Syed M. Zubair,et al.  An Improved Design and Rating Analyses of Counter Flow Wet Cooling Towers , 2001 .

[30]  Detlev G. Kröger,et al.  A critical investigation into the heat and mass transfer analysis of counterflow wet-cooling towers , 2005 .

[31]  Kuppan Thulukkanam Heat Exchanger Design Handbook , 2013 .

[32]  D. Baker,et al.  a comprehensive approach to the analysis of cooling tower performance , 1961 .

[33]  Robin Smith,et al.  Cooling water system design , 2001 .

[34]  Arturo Jiménez-Gutiérrez,et al.  Optimization model for re-circulating cooling water systems , 2010, Comput. Chem. Eng..