Inherent flammability parameters—Room corner test application
暂无分享,去创建一个
It has been hypothesized that four parameters are solely responsible for a material's performance in a flammability scenario. This excludes effects of material physical integrity, i.e. melting, delamination, etc. They are (1) the critical heat flux below which piloted ignition cannot occur (CHF), (2) the ratio of heat of combustion to heat of gasification (HRP), (3) the thermal response parameter related to the thermal inertia and the ignition temperature (TRP), and (4) the available energy per unit area (AEP). The fire scenario controls the process by its initial heat flux and region of ignition. The hypothesis is applied to 54 tests of the ISO Room Corner Test to assess its validity. It is shown that these four parameters give good correlations in predicting the time to flashover and whether it occurs. In principle, different correlations could be developed for other scenarios of tests and fire configurations. Copyright © 2009 John Wiley & Sons, Ltd.
[1] J. Panagiotou. A Methodology for Flammability Diagrams , 2004 .
[2] A. F. Roberts,et al. A Limiting condition for the burning of flammable liquids , 1973 .
[3] James G. Quintiere. A theoretical basis for flammability properties , 2006 .