Study on Restraining DC Neutral Current of Transformer During HVDC Monopolar Operation

HVDC transmission system operating in ground return mode often affects the neighboring ac power system seriously. This paper presented some field experimental results, including audible noise, voltage harmonics, and oscillation of the transformer while dc current passes through the neutral point. The relationship between the dc neutral current and those effects were discovered clearly by analyzing these data. Based on the analysis of the characteristics of the dc current distributed under ground and in the ac network, some useful measures to decrease or block the dc current through the neutral point of the transformer, such as the injection of reverse dc current, blocking capacitor, and series resistor are compared. And the series resistor method is chosen after carefully study of its feasibility in the ac power system. The parameters as well as the protection method of the resistor were selected by implementing several large current experiments. Finally, field experiments were carried out to observe the effect of reducing the neutral current with a series resistor device. Experimental results show that series resistor method is a simple structure, low cost, and of high reliability, which can restrain the neutral current effectively.

[1]  Zhang Qiang ANALYSIS ON INFLUENCE OF GROUND ELECTRODE CURRENT IN HVDC ON AC POWER NETWORK , 2005 .

[2]  Jinliang He,et al.  Numerical Analysis of DC Current Distribution in AC Power System Near HVDC System , 2008, IEEE Transactions on Power Delivery.

[3]  W. A. Radasky,et al.  Impacts of geomagnetic storms on EHV and UHV power grids , 2010, 2010 Asia-Pacific International Symposium on Electromagnetic Compatibility.

[4]  C. M. Portela,et al.  Correction to "Calculation of electric field and potential distributions into soil and air media for a ground electrode of a HVDC system" , 2004 .

[5]  K. R. Padiyar Hvdc Power Transmission Systems: Technology and System Interactions , 1991 .

[6]  D. Mukhedkar,et al.  Evaluation of the voltage distribution around toroidal HVDC ground electrodes in n-layer soils , 1988 .

[7]  Jos Arrillaga,et al.  High Voltage Direct Current Transmission , 2014 .

[8]  Wu Xiao-chen ANALYSIS ON OPERATIONAL PROBLEMS IN SOUTH CHINA AC-DC HYBRID POWER GRID , 2004 .

[9]  Guangzheng Ni,et al.  3-D nonlinear transient eddy current calculation of online power transformer under DC bias , 2005, IEEE Transactions on Magnetics.

[10]  D. L. Carlson,et al.  GIC mitigation: a neutral blocking/bypass device to prevent the flow of GIC in power systems , 1991 .

[11]  D. McGillis,et al.  Review of the design of the James Bay-Boston DC system , 1991 .

[12]  William A. Radasky,et al.  Geomagnetic storm forecasts and the power industry , 1997 .

[13]  Cai Xi-peng ANALYSIS ON FREQUENT SWITCHING OF AC FILTER IN TIANGUANG HVDC PROJECT , 2005 .

[14]  M. Sublich,et al.  Alternatives for blocking direct current in AC system neutrals at the Radisson/LG2 complex , 1992 .

[15]  R. J. Ringlee,et al.  IEEE Power Engineering Society , 1989 .

[16]  William A. Radasky,et al.  SPACE WE ATHER FROM A USER'S PERSPECTIVE : GEOMAGNETIC STORM FORECASTS ANDTHE POWER INDUSTRY , 1997 .

[17]  L. Bolduc,et al.  Development of a DC current-blocking device for transformer neutrals , 2005, IEEE Transactions on Power Delivery.