Nonlinear model-based dissolved oxygen control in a biological wastewater treatment process

The dissolved oxygen (DO) concentration has been an important process parameter in the biological wastewater treatment process (WWTP). In this paper, we propose a nonlinear control scheme to maintain the dissolved oxygen level of an activated sludge system. Without any linearization or model reduction, it can directly incorporate the nonlinear DO process model with on-line estimation of the respiration rate (R) and the oxygen transfer rate (KLa). Simulation results show that it outperforms a control performance of the PID controller. Since it incorporates the process disturbance and nonlinearity in the controller design, the suggested method can efficiently deal with the operating condition changes that occur frequently in the wastewater treatment process.

[1]  Carl-Fredrik Lindberg,et al.  Control and estimation strategies applied to the activated sludge process , 1997 .

[2]  G. R. Sullivan,et al.  Generic model control (GMC) , 1988 .

[3]  Peter L. Lee,et al.  GENERIC MODEL ADAPTIVE CONTROL , 1992 .

[4]  B. Carlsson,et al.  ON-LINE ESTIMATION OF THE RESPIRATION RATE AND THE OXYGEN TRANSFER RATE AT KUNGSANGEN W ASTEW ATER TREATMENT PLANT IN UPPSALA , 1994 .

[5]  B. Carlsson On-Line Estimation of the Respiration Rate in an Activated Sludge Process , 1993 .

[6]  Bengt Carlsson,et al.  Nonlinear and set-point control of the dissolved oxygen concentration in an activated sludge process , 1996 .

[7]  Stefano Marsili-Libelli,et al.  Estimation of respirometric activities in bioprocesses , 1997 .

[8]  Peter L. Lee,et al.  System identification for generic model control , 1999 .

[9]  Gustaf Olsson,et al.  SIMULTANEOUS DO CONTROL AND RESPIRATION ESTIMATION , 2002 .

[10]  Petre Stoica,et al.  Decentralized Control , 2018, The Control Systems Handbook.

[11]  B. Carlsson,et al.  Estimation of the respiration rate and oxygen transfer function utilizing a slow do sensor , 1996 .

[12]  C. Alafodimos State Estimation for a Large Scale System , 1985, 1985 American Control Conference.

[13]  Gustaf Olsson,et al.  Simultaneous DO Control and Respiration Estimation , 1989 .

[14]  C K Yoo,et al.  Closed-loop identification and control application for dissolved oxygen concentration in a full-scale coke wastewater treatment plant. , 2001, Water science and technology : a journal of the International Association on Water Pollution Research.