A New Cross-Correlation Algorithm Based on Distance for Improving Localization Accuracy of Partial Discharge in Cables Lines

Locating the partial discharge (PD) source is one of the most effective means to locate local defects in power cable lines. The sampling rate and the frequency-dependent characteristic of phase velocity have an obvious influence on localization accuracy based on the times of arrival (TOA) evaluation algorithm. In this paper, we present a cross-correlation algorithm based on propagation distance to locate the PD source in cable lines. First, we introduce the basic principle of the cross-correlation function of propagation distance. Then we verify the proposed method through a computer simulation model and investigate the influences of propagation distance, sampling rate, and noise on localization accuracy. Finally, we perform PD location experiments on two 250 m 10 kV XLPE power cables using the oscillation wave test system. The simulation and experiment results indicate that compared with traditional TOA evaluation methods, the proposed method has superior locating precision.

[1]  Tao Jin,et al.  A Novel Adaptive EEMD Method for Switchgear Partial Discharge Signal Denoising , 2019, IEEE Access.

[2]  S. M. Strachan,et al.  Partial discharge location in power cables using a double ended method based on time triggering with GPS , 2013, IEEE Transactions on Dielectrics and Electrical Insulation.

[3]  Sheng Lan,et al.  Partial discharge location of power cables based on an improved phase difference method , 2019, IEEE Transactions on Dielectrics and Electrical Insulation.

[4]  A. Akbari,et al.  Partial Discharge Localization on Power Cables Using On-Line Transfer Function , 2019, IEEE Transactions on Power Delivery.

[5]  P.A.A.F. Wouters,et al.  Accurate estimation of the time-of-arrival of partial discharge pulses in cable systems in service , 2008, IEEE Transactions on Dielectrics and Electrical Insulation.

[6]  Dandan Zhang,et al.  Local degradation diagnosis for cable insulation based on broadband impedance spectroscopy , 2015, IEEE Transactions on Dielectrics and Electrical Insulation.

[7]  Ivo Palu,et al.  Performance Comparison of PD Data Acquisition Techniques for Condition Monitoring of Medium Voltage Cables , 2020 .

[8]  Lu Lu,et al.  A Novel Oscillation Wave Test System for Partial Discharge Detection in XLPE Cable Lines , 2020, IEEE Transactions on Power Delivery.

[9]  Kay Rethmeier,et al.  An overview on the current status of partial discharge measurements on AC high voltage cable accessories , 2016, IEEE Electrical Insulation Magazine.

[10]  F. Kreuger,et al.  Partial discharge. XVIII. Errors in the location of partial discharges in high voltage solid dielectric cables , 1993, IEEE Electrical Insulation Magazine.

[11]  Chengke Zhou,et al.  A novel on-line cable pd localisation method based on cable transfer function and detected pd pulse rise-time , 2015, IEEE Transactions on Dielectrics and Electrical Insulation.

[12]  Kimmo Kauhaniemi,et al.  Online condition monitoring of MV cable feeders using Rogowski coil sensors for PD measurements , 2019, Electric Power Systems Research.

[13]  A. Piersol Time delay estimation using phase data , 1981 .

[14]  Zhousheng Zhang,et al.  Rogowski air coil sensor technique for on-line partial discharge measurement of power cables , 2009 .

[15]  Kemin Zhou,et al.  An Improved Denoising Method for Partial Discharge Signals Contaminated by White Noise Based on Adaptive Short-Time Singular Value Decomposition , 2019, Energies.

[16]  Gehao Sheng,et al.  Robust Time Delay Estimation Method for Locating UHF Signals of Partial Discharge in Substation , 2013, IEEE Transactions on Power Delivery.

[17]  G. B. Gharehpetian,et al.  A New Partial Discharge Signal Denoising Algorithm Based on Adaptive Dual-Tree Complex Wavelet Transform , 2018, IEEE Transactions on Instrumentation and Measurement.

[18]  Anan Zhang,et al.  Propagation coefficient spectrum based locating method for cable insulation degradation , 2019, IET Science, Measurement & Technology.

[19]  Koichi Ichige,et al.  Accurate estimation of minimum filter length for optimum FIR digital filters , 2000 .

[20]  A. Cavallini,et al.  A novel method to locate PD in polymeric cable systems based on amplitude-frequency (AF) map , 2007, IEEE Transactions on Dielectrics and Electrical Insulation.

[21]  R Mardiana,et al.  Partial discharge location in power cables using a phase difference method , 2010, IEEE Transactions on Dielectrics and Electrical Insulation.